Carrier 17EX Start-Up, Operation And Maintenance Instructions Manual page 24

Externally geared centrifugal liquid chillers
Table of Contents

Advertisement

To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS02.
4. Press SELECT .
DESCRIPTION
Hot Gas Bypass Relay
*Chilled Water Pump
Chilled Water Flow
*Condenser Water Pump
Condenser Water Flow
Compressor Start Relay
Compressor Start Contact
Compressor Run Contact
Starter Fault Contact
Pressure Trip Contact
Single Cycle Dropout
Oil Pump Relay
Oil Heater Relay
Motor Cooling Relay†
Auxiliary Oil Pump Relay
*Tower Fan Relay
Compr. Shunt Trip Relay
Alarm Relay
Spare Prot Limit Input
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
1. Press
MENU
.
2. Press STATUS .
3. Scroll down to highlight STATUS03.
4. Press SELECT .
DESCRIPTION
OPTIONS BOARD 1
*Demand Limit 4-20 mA
*Temp Reset 4-20 mA
*Common CHWS Sensor
*Common CHWR Sensor
*Remote Reset Sensor
*Temp Sensor — Spare 1
*Temp Sensor — Spare 2
*Temp Sensor — Spare 3
OPTIONS BOARD 2
*4-20 mA — Spare 1
*4-20 mA — Spare 2
*Temp Sensor — Spare 4
*Temp Sensor — Spare 5
*Temp Sensor — Spare 6
*Temp Sensor — Spare 7
*Temp Sensor — Spare 8
*Temp Sensor — Spare 9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
Table 2 — LID Display Data (cont)
EXAMPLE 2 — STATUS02 DISPLAY SCREEN
POINT TYPE
INPUT
OUTPUT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
EXAMPLE 3 — STATUS03 DISPLAY SCREEN
RANGE
4-20
4-20
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
4-20
4-20
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
24
UNITS
OFF/ON
OFF/ON
NO/YES
OFF/ON
NO/YES
OFF/ON
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
NORMAL/ALARM
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
NORMAL/ALARM
ALARM/NORMAL
REFERENCE POINT NAME
UNITS
mA
mA
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
mA
mA
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
REFERENCE POINT NAME
(ALARM HISTORY)
HGBR
CHWP
EVFL
CDP
CDFL
CMPR
1CR
AUX
RUN
AUX
STR
FLT
PRS
TRIP
V1
CYCLE
OILR
OILH
MTRC
AUXOILR
TFR
TRIPR
ALM
SPR
PL
(ALARM HISTORY)
DEM
OPT
RES
OPT
CHWS
CHWR
R
RESET
SPARE1
SPARE2
SPARE3
SPARE1
M
SPARE2
M
SPARE4
SPARE5
SPARE6
SPARE7
SPARE8
SPARE9