ESP PLATINUM QUE SPLIT DUCTED UNIT INSTALLATION AND COMMISSIONING GUIDE - OUTDOOR OUDOOR UNITS ESP PLATINUM CRQ2-14AS CRQ3-17AS CRQ4-19AS INDOOR UNITS ESP PLATINUM ERQ2-14AS ERQ3-17AS ERQ4-19AS Please Read This Guide Congratulations on your purchase of an Actron Air air conditioning unit. This unit has been designed and manufactured with the highest quality standard in mind.
TABLE OF CONTENTS For optimum efficiency, your air conditioning unit will For optimum efficiency, your air conditioning unit will General Information............. deliver just the right amount of cooling or heating capacity deliver just the right amount of cooling or heating capacity Safety Instructions............
R410A is only charged in liquid form on the discharge that R410A is only charged in liquid form on the discharge ActronAir indoor unit as specified in the Technical side. Take into consideration the correct amount of side. Take into consideration the correct amount of Selection Catalogue.
3. Minimum service access areas and spaces for airflow clearances are OUTDOOR COIL responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow. HEIGHT CLEARANCE = 1500 4.
Page 8
3. Minimum service access areas and spaces for airflow clearances are OUTDOOR COIL responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow. 4. Under all circumstances, condenser air must not recirculate back onto condenser coil.
1000mm between the units or between the unit and the outside perimeter is available. 3. Minimum service access areas and spaces for airflow clearances are responsibilities of the installer, ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow.
FIELD PIPE CONNECTION CAUTION The units described in this guide uses R410A refrigerant, which operates at a pressure approximately 1.6 times higher than a similar systems using R-22. When installing equipment using R410A refrigerant, there are number of standards that must be met: •...
Page 13
2 x 450 mm Spigots ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase. SRD175C-0100 / SRD175E-0100 -P1- 090326...
Page 14
FIELD PIPE CONNECTION AL & SELECTION DATA SRD175C / SRD175E ESP SPLIT DUCTED UNIT CAUTION Brazed joints should only be made while purging Nitrogen through the system. Brazed joints should only be made while purging Nitrogen through the system. Failure to do so will cause carbon deposit to be left on the internal pipe surface, Failure to do so will cause carbon deposit to be left on the internal pipe surface, that in turn can cause system failure and void of warranty.
(Single Phase + Neutral) 50Hz (2 Core Shielded Twisted Pair 7/0.30 (0.5mm ) Data Cable)* * DO NOT USE the 2 Core Orange Shielded Data Cable (AEDC1) used on previous ActronAir units. INDOOR UNIT SUB-MAINS CIRCUIT BREAKER MAIN SUPPLY FROM...
Page 18
ASSY CASING 8011-652-RENDER 0.1/~0 MATERIAL: FINISH: 0.5 / m 0.5 / m ActronAir Pty Ltd This drawing always remains the See Notes See Notes Compressor ONLY will cycle OFF and remain off 5 Irvine Place intellectual property of Actron Norwest Business Park Engineering Pty Ltd.
AEDC2 DATA CABLE P-CLIP SHIELDING INSTRUCTIONS Step 1: Step 1: Step 2: Step 2: • • Strip approximately 100mm of outer insulation off Strip approximately 100mm of outer insulation off • • Twist the core wires together. Twist the core wires together. AEDC2 Data cable.
The system of this unit operates with PVE oil that rapidly absorbs moisture. The maximum time any system can be opened to atmosphere is 15 minutes. The maximum time any system can be opened to atmosphere is 15 minutes. REFRIGERANT CHARGE DETAILS CRQ2-14AS CRQ3-17AS CRQ4-19AS Refrigerant Type...
Page 24
Allow the systems to stabilise (15-30 mins) and repeat the step 1-3 until superheat falls within the range specified in the table below. SUBCOOL AND SUPERHEAT TABLE COOLING HEATING Nominal Indoor MODELS Airflow (L/s) SUBCOOL SUPERHEAT SUBCOOL SUPERHEAT CRQ2-14AS ± ± ± ± CRQ3-17AS ± ± ± ± CRQ4-19AS ±...
MAINTENANCE FREQUENCY CHECKLIST Electrical Service Frequency Parts Detail of Service Check Service Methods Printed Circuit Tighten Terminals as necessary on Visual Inspection Boards printed circuit boards Check all electrical Electrical terminals, mains, Re-tighten if loose. Connections communications, etc Magnetic Check for loose terminal Tighten electrical terminals.
TROUBLE SHOOTING GUIDE Fault Possible Causes Remedies The system does not Built-in safety timers have been Wait for up to 20 minutes is passed from turn start. activated on time. A breaker has turned OFF or a fuse Check breakers and fuses. has blown.
Page 30
TROUBLE SHOOTING GUIDE FAULT AND STATUS CODES QT*-1000, ZT*-100 Outdoor master controller zone Unit Category FUNCTION / FAULT (Main Screen) controller - Tech Menu (E02) Room Sensor Error (open or short circuit) - Tech Menu (E03) - Tech Menu (E04) Indoor Coil Inlet Sensor Error (open or short circuit) - Tech Menu (E06) High Discharge Temp.
Page 32
2. Nominal airflow is the air supplied by the air conditioners at its standard rating conditions. This data can be found in the ActronAir technical catalogue or by contacting technical support on 1800 119 229 and quoting the applicable unit model.
START UP AND COMMISSIONING REPORT Installation Details Customer Name: Customer Address: Site Address: Installer MUST complete their contact details on the wall controller via Menu → Settings → Edit servicing contact details. Complete the information below for future reference. Supply Air Temperature C Discharge Temperature Return Air Temperature C Suction Pressure...