Page 1
BMS MODBUS 485 Installation and Commissioning Guide BMS Modbus is available for compatible units with an UNO Outdoor Board such as: Variable Classic 2 Advance Capacity Condenser Condenser Commercial • CRV290T • CRA100S • CRV140S • CRV330T • CRA130S • CRV160S ICUNO-MOD •...
UNO OUTDOOR BOARD AUX 485 DUCT RAIL INTERCONNECTION CABLE: ENSURE TO ROUTE THIS CABLE THROUGH THE DUCT RAIL. ICUNO-MOD OUTDOOR AUX NOTE: The layout will differ between ActronAir systems. Installation and Commissioning Guide ICUNO-MOD Doc. No. 9590-3013 Ver. 5 200722...
Step 3. Test unit with multimeter to ensure there is no power, before starting installation of the BMS card. Step 4. Use supplied PCB Mounts to mount ICUNO-MOD into correct location. NOTE: Location will differ between ActronAir systems. Step 5. Install BMS ICUNO-MOD as shown below.
ICUNO-MOD Installation and Commissioning Guide 04.05. BMS Configuration of ICUNO-MOD Card Consult project system designer (BMS engineer or similar role) for the correct Modbus RS-485 configuration for this unit. Use the DIP switches on the BMS Card to configure the Modbus parameters. New BMS configuration will take effect when the BMS card initializes, either by the RESET button or power cycle.
Status 2 LED (white) will FLASH (once every 2 seconds). The BMS card will not accept any BMS commands during this time. Step 3. After 60 seconds the Amber Status LED should be ON, indicating a stable connection to the ActronAir Air Conditioning System.
Open and Close zones The ActronAir AC system may be configured to operate in Basic BMS Control, or Basic BMS Control with a Wall Control. When operating in Basic BMS Control with a Wall Control, all settings changes from the BMS and Wall Control will be synchronized across the entire system.
ICUNO-MOD Installation and Commissioning Guide A Wall Control can not be used if the ActronAir AC system is configured for Advanced BMS Control. Additional information for controlling the unit in Advanced BMS Control can be found in Section 05.02. 04.07.05. UNO Configuration...
Page 16
• See Section 05 for instructions on configuring UNO Outdoor Board for BMS Control. If the above steps fail to fix the problem. Contact ActronAir Technical Support on 1800 119 229 for further assistance. Installation and Commissioning Guide ICUNO-MOD Doc. No. 9590-3013 Ver. 5 200722...
Installation and Commissioning Guide 05. BMS Control This section of the document provides a guide to using the ActronAir BMS Table. This section explores the Modbus registers relevant to each BMS Operation Mode, their usage and meaning to control the various units.
5008 * Fan speed PWM limits can be set from the ActronAir units service menu. Consult the Air Conditioner units installation guide for more information. If system has been configured as a single speed indoor fan Register 4 - Supply fan mode can only be set to MEDIUM speed.
Analog 5008 1. ActronAir software ensures that system operational safety is retained by maintaining minimum and maximum safe compressor demand and fan speed demand. Consult the Air Conditioner unit’s installation guide for safe operating limits. 2. Actual system running capacity (Modbus Analog 801) and Indoor Fan1 Speed (Modbus Analog 1311) will reflect the Set...