Do not apply battery power until it is determined that A and
B battery cables with isolated returns and power cables are
wired correctly. With power applied, reverse polarity on wir-
ing (+batt wired to -batt pin on connector) can cause power
supply fuse to blow.
Grounding of pole, antenna, customer interfaces, and all entrances to
the building interior shall meet local electrical code and standard
business practices.

E1 CONNECTIONS

3.3
Recommended connectorized cable assembly – PN 3CC52118AA (22 AWG 34 pair shielded,
jacketed cable with 68-pin SCSI connector on each end). See Figure 3-3 and Figure 3-3 for
connections. Refer to Table 3-1 and Table 3-2 for mating cable wiring.
Figure 3-3 E1 Signal Cable and Connector