Lifting And Leveling; Setting Without A Crane - Hussmann Scroll Plus Fibertronic 401789 Installation And Service Manual

Table of Contents

Advertisement

September 1, 1997

LIFTING AND LEVELING

Using rigging with a spreader bar, the Scroll Plus
System may be lifted into position. The spreader
bar is required to prevent damage to the unit.
Note: This unit is front heavy, due to the control
Panel(s), and compressor locations. Take neces-
sary precautions when lifting, and lift only from
lower base support feet.
Vibration isolation pads are supplied with each
rack. The entire weight of the rack must rest on
these pads, with the rack cross leveled. To adjust
for slightly uneven floors, place 16 gauge 3 x 3
galvanized steel shims between the pads and the
floor. (Shims must be field supplied.)
Return to Contents
Use Appropriate Spreader Bars
Two 1" Pads
1" Pads Under
Front and Back
Center Support
Figure 1-4 — Lifting and Leveling the Scroll Plus System

SETTING WITHOUT A CRANE

In many locations crane lifting may not be prac-
tical. Where possible use equipment dollies
centered under each foot, or Johnny Bars. Do
not push or pull on any of the pipes, valves,
accessories, or control panels when moving the
Scroll Plus System.
For mezzanine installations, a fork lift (operated
within its height and weight limits) may be used
to raise the Rack into position.
Caution: The unit is front heavy due to the
control panel(s), and compressor locations. Take
necessary precautions when lifting, and lift only
from lower base support feet.
Two 1" Pads
Front and Back
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
P/N 401789
1 - 5