The data of the columns in the "SNMP Write" have the following meanings:
If the field "Enable" is checked,
the SNMP OID is enabled;
In the field
"Community
the name of the Community is
defined;
In the field "Type" the type of
data of the OID is defined (Octet
String or Integer);
In
the
field
"Position"
starting
byte
of
the
memory array where mapping
the data is defined;
In the field
"Start
Bit" the starting bit of the selected Position is defined;
In the field
"Num
Bits/Bytes" the dimension of the OID is defined. For 'Int' type the dimension is in bit, for 'String' type the
dimension is in bytes;
In the field "Description" the description/name of the OID is defined;
In the field "Conversion" it is possible to select the data conversion to apply to the data;
In the field "Mnemonic" a brief description of the OID is defined.
Note:
If the fields "On Change" and "On Timer" are disabled, the OID is readable using standard GET command. If one of these fields is
enabled, the OID is sent as Trap and it is readable by GET command too.
Note:
The field "Description" must start with lowercase letter and it cannot contain special chars (just letters and numbers). All the
"Description" fields must be different between them.

SNMP MIB:

By pressing the
"SNMP
MIB" button it is possible to save the MIB file for the SNMP Agent.
ADFweb.com Srl – IT31010 – Mareno – Treviso
Name"
the
internal
Figure 5b: "Set SNMP Access -> SNMP Write" window
User Manual OPC UA Server / SNMP Agent
Document code: MN67B48_ENG
Revision 1.000
INFO:
www.adfweb.com
Page 19 of 25
Phone +39.0438.30.91.31

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HD67B48-B2 and is the answer not in the manual?

This manual is also suitable for:

Hd67b23Hd67b47Hd67b48

Table of Contents