GE Profile JD968 Installation Instructions Manual page 7

Self-cleaning radiant electric drop-in range
Table of Contents

Advertisement

Installation Instructions
Electrical Connections
C
THREE-CONDUCTOR BRANCH
CIRCUIT CONNECTION
When connecting to a 3-conductor branch
circuit, if local codes permit:
Connect the bare oven ground
C7a
conductor with the crimped neutral
(white) lead to the branch circuit
neutral (white or gray in color),
using wire nuts.
Connect the oven red lead to the
C7b
branch circuit red lead, and the oven
black lead to the branch circuit black
lead in accordance with local codes,
using wire nuts. If the residence red,
black or white leads are aluminum
conductors, see "WARNING" note
(See page 6).
Range Conduit
Snaps Into Box
Red
Ground and
Neutral Wires
(White)
Black
Branch
Circuit
Alternate
Knockout
Neutral Bare Wire
Connection
cont.
NEW CONSTRUCTION AND
FOUR-CONDUCTOR BRANCH
CIRCUIT CONNECTION
• When installing in new construction, or
• When installing oven in a mobile home or
recreational vehicle, or
• When local codes do not permit grounding
through neutral:
Cut the neutral (white) lead from the
C7a
crimp. Re-strip the neutral (white)
lead to expose the proper length of
conductor and connect it to the white
or gray branch circuit neutral in
accordance with local code using
wire nuts.
Attach the appliance grounding lead
C7b
(green or bare copper) in accordance
with local codes. If the residence
grounding conductor is aluminum,
see WARNING note (See page 6).
Connect the oven red lead to the
C7c
branch circuit red lead and the oven
black lead to the branch circuit black
lead in accordance with local codes,
using wire nuts. If the residence red,
black or white leads are aluminum
conductors, see "WARNING" note
(See page 6).
Range Conduit
Snaps Into Box
Red
White
7
Black
Branch
Circuit
Ground
Wires
Alternate
Knockout
(Continued on following page)