drain the refrigerant to the outside. Take care that the drained refrigerant will not
cause any danger. In doubt, one person should guard the outlet. Take special care
that drained refrigerant will not float back into the building.
Evacuate the refrigerant circuit.
Purge the refrigerant circuit with nitrogen for 5 min.
Evacuate again.
Cut out the compressor and drain the oil.
Transportation, marking and storage for units that employ flammable refrigerants
Transport of equipment containing flammable refrigerants
Attention is drawn to the fact that additional transportation regulations may exist with
respect to equipment containing flammable gas. The maximum number of pieces
of equipment or the configuration of the equipment, permitted to be transported
together will be determined by the applicable transport regulations.
Marking of equipment using signs
Signs for similar appliances used in a work area generally are addressed by local
regulations and give the minimum requirements for the provision of safety and/or
health signs for a work location. All required signs are to be maintained and employers
should ensure that employees receive suitable and sufficient instruction and training
on the meaning of appropriate safety signs and the actions that need to be taken in
connection with these signs. The effectiveness of signs should not be diminished by
too many signs being placed together. Any pictograms used should be as simple as
possible and contain only essential details.
Disposal of equipment using flammable refrigerants
See national regulations.
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer's
instructions. Storage of packed (unsold) equipment Storage package protection
should be constructed such that mechanical damage to the equipment inside the
package will not cause a leak of the refrigerant charge. The maximum number of pieces
of equipment permitted to be stored together will be determined by local regulations.