Fault Finding; Display Faults - Ideal Heating i305 Installation & Servicing

Pod heat interface unit
Table of Contents

Advertisement

4.

FAULT FINDING

4.1 DISPLAY FAULTS

Display
F1
HOT WATER
PREHEAT
OFF
F2
HOT WATER
PREHEAT
OFF
f4
HOT WATER
PREHEAT
OFF
F5
HOT WATER
PREHEAT
OFF
F6
HOT WATER
PREHEAT
OFF
F7
HOT WATER
PREHEAT
OFF
48
SECTION 4 - FAULT FINDING
Fault
Check system water pressure is between 1 and 1.5 bar on the system
pressure gauge. If system pressure is low top up the CH circuit as per the
steps in Section 2.5. If system pressure is higher than 1.5 bar ensure the
Low Water Pressure
system is cold and carefully reduce the pressure using the draining point
on a system radiator. If fault persists, replace water pressure switch (see
Section 3.15).
Ensure primary circuit is correctly pressurised and primed to the correct
operating temperatures. Check primary circuit is fully open and all isolation
No change in DHW
valves at base of HIU are open. Ensure all air is purged from primary circuit.
Temperature during
If a CCV (credit control valve) is installed in appliance, ensure dwelling has
demand period
sufficient credit to open valve and wiring to valve has good continuity – Refer
to CCV installer and servicing guide for details.
Remove harness to CH clip on flow thermistor and using a multi-meter
measure the resistance of the thermistor – This should be around 10kΩ in
Flow Thermistor
ambient conditions. If thermistor is functioning correctly reconnect harness
Fault
to flow thermistor and reset unit. If thermistor is not functioning correctly
replace item. If fault persists, replace PCB (see Section 3.20).
Remove harness to return to CH clip on thermistor and using a multi-meter
measure the resistance of the thermistor – This should be around 10kΩ in
Return Thermistor
ambient conditions. If thermistor is functioning correctly reconnect harness
Fault
to flow thermistor and reset unit. If thermistor is not functioning correctly
replace item. If fault persists, replace PCB (see Section 3.20).
Remove outside sensor wiring from screw terminals on the back off the HIU
controls enclosure (see Section 2.9 for wiring locations). Using a multi-meter
check resistance and continuity to outside sensor:
At 0°C expect 31,000 - 35,000 Ohms
Outside Sensor
At 15°C expect 15,000 - 16,500 Ohms
Open Circuit
At 30°C expect 7,700 - 8,500 Ohms
If the thermistor has an open circuit or short circuit replace outside sensor
and wiring to outside sensor. Reset the HIU. If problem persists, replace
PCB.
Contact a qualified electrician, the building manager, or the electricity
Incorrect Mains
Voltage
provider.
Action
Installation and Servicing
Continued....