M-system R3-AR4 Instruction Manual page 2

Rtd input alarm module

Advertisement

COMPONENT IDENTIFICATION
■ FRONT VIEW
RUN LED
ERR LED
11
12
13
14
15
16
17
18
19
20
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with burnout;
Green in normal operating conditions.
■ SIDE VIEW
1
2
3
4
5
6
7
8
9
10
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SW3
Conv.
4
Rate
3
Temp.
2
Unit
1
Burnout
ON
■ SIDE DIP SW
(*) Factory setting
• RTD Type: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
INPUT 3 (SW2)
INPUT 4 (SW2)
1
2
3
4
5
OFF OFF OFF OFF OFF OFF OFF OFF
ON OFF OFF OFF ON OFF OFF OFF Pt 100 (JIS '89)
OFF ON OFF OFF OFF ON OFF OFF JPt 100 (JIS '89)
ON ON OFF OFF ON ON OFF OFF Pt 50 Ω (JIS '81)
OFF OFF ON OFF OFF OFF ON OFF Ni 100
ON OFF ON OFF ON OFF ON OFF Cu 10 @ 25°C
OFF ON ON OFF OFF ON ON OFF Pt 1000
ON ON ON OFF ON ON ON OFF Ni 508.4 Ω
OFF OFF OFF ON OFF OFF OFF ON Cu 50
• Burnout: SW3-1
SW3-1
OFF
ON
• Temperature Unit: SW3-2, 3-3
SW3-2
OFF
ON
OFF
• Conversion Rate: SW3-4
SW3-4
OFF
ON
R3-AR4
Functions
SW2
SW1
RTD
8
8
Input 2 (SW1)
7
7
or
6
6
Input 4 (SW2)
5
5
4
4
Input 1 (SW1)
3
3
or
2
2
Input 3 (SW2)
1
1
ON
ON
RTD
6
7
8
Pt 100 (*)
(JIS '97, IEC)
BURNOUT
Upscale (*)
Downscale
SW3-3
TEMP. UNIT
OFF
°C (*)
OFF
°F
ON
(Absolute Temp)
CONV. RATE
250 msec. (*)
1 sec.
EM-8433 Rev.3 P. 2 / 4