M.3.5.2 Top isolators
▪
Unscrew both failsafe bolts and remove the failsafe configuration shown in Figure
M-40 using a 5 mm Allen key or a 10 mm spanner.
▪
Then unscrew the M6 nut from the isolator and remove the fittings from all four top
isolators as shown in Figure M-40 and Figure M-41.
Failsafe bolt
Top locking piece
Figure M-40: Unscrew the failsafe bolt
Figure M-41: Loosen the isolator M6 nut using a nut spinner
MA-005 - Minitrans Installation Manual - Rev 4.5
M6 nut
13-Aug-20
Page 84 of 86