Appendix J Heat Trace Cable - GE Kelman Minitrans Installation Manual

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman Minitrans:
Table of Contents

Advertisement

It is recommended that heat trace cable be used on the tubing, if the oil temperature in
the tubing can reach temperatures below −10 °C.
The customer is responsible for supplying the heat trace cable, which must be installed
by a qualified electrician. GE Service Personnel are available to advise the customer and
work with the company's electrician to install the heat trace cable.
J.1
Installation Requirements
Installation of heat trace cable must be done by a qualified electrician familiar with
local wiring regulations.
The heat trace cable selected shall have all necessary safety approvals required by
local wiring regulations. The heat trace cable rating shall be suitable for the voltage of
the power source, the temperature rating required, and the size of tubing it is to be
installed on.
Heat trace cable must be installed in accordance with the manufacturer's
instructions and local wiring regulations. Particular attention should be paid to
requirements for circuit protection and power supply.
The heat trace cable shall be controlled by a thermostat to prevent continuous
operation.
MA-005 - Minitrans Installation Manual - Rev 4.5
Appendix J
Heat Trace Cable
13-Aug-20