Fault messages
(cont.)
Display
Explanation/Cause/Effect
indication
In 581
Hopper almost empty (the level
switch has responded).
The boiler continues to heat
until the remaining fuel has
been used up.
In 582
Hopper empty; burner blocked.
In 595
The combustion chamber door
is open.
The boiler completely burns the
available fuel.
Fault messages resulting in a shutdown
These fault messages are indicated by code "AL".
After the relevant fault has been removed, press the reset button prior to start-
ing the boiler again.
Display
Explanation/Cause/Effect
indication
AL 005
Grate shaker blocked
Grate shaker motor or limit
switch faulty.
The boiler completely burns the
available fuel.
AL 006
Supply auger motor faulty.
The boiler completely burns the
available fuel; the induced fan
is switched off immediately.
AL 016
Impeller of the induced fan con-
taminated.
Induced draught fan faulty.
Set speed cannot be achieved.
The boiler completely burns the
available fuel.
Troubleshooting
Remedy
Start the pellet supply or wait for/
change the enable time.
Start the pellet supply or wait for/
change the enable time.
Close the combustion chamber
door.
Remedy
Clean the burner pot (see
page 12).
Replace motor or limit switch.
Replace motor.
Clean the impeller (see
page 13).
Replace fan motor.