Transformer - Econar GeoSource 2000 GW Series Installation And Operating Instructions Manual

Hydronic
Table of Contents

Advertisement

E.
Application Diagrams
Figures
1
through
5
show
the
components
of
a
hydronic
heat
pump
system discussed above used
in
some
common
applications. These
figures
by
no
means
represent
all
the
possible
hydronic
heat
pump
applications,
but they
do
show
some
important
principals
that
can
be applied to
any
system.
VII. ELECTRICAL
SERVICE
e
Note
-
Always refer to
the inside
of
the electrical
box
cover
for
the
correct
wiring
diagram,
and
always
refer
to
the
nameplate
on the exterior
of
the
cabinet
for
the
correct
electrical specifications.
9WARNING
_
ELECTRICAL SHOCK CAN
CAUSE
PERSONAL
INJURY OR DEATH.
Disconnect
all
power
supplies
before installing
or
servicing
electrical
devices.
Only
trained and
qualified
service
personnel
should install, repair
or
service
this equipment'
gwARNtr.iG
-
THEUNIT
MUST
BE
PROPERLY
GROUNDED:
The main
electrical
service must
be
protected
by
a
fuse
or
circuit
breaker and
be
capable
of
providing the
amperes
required by
the
unit
at
nameplate voltage.
A11
wiring
must
comply
with
the
national electrical
code
and,/or
any
local
codes
that may apply. Access
to
the
line
voltage contactor
is
through the knockouts provided
on
either
side
of
the
heat
pump next to
the
front
corner. Route
EMT
or
flexible
conduit
with
appropriate
whe
to
the
contactor.
Ensure adequate
supply
wiring
to
minimize the
level
of
dimming lights during
compressor startup on
single-phase
installations.
Some
dimming is
normal, and a variety
of
stafi-assist
accessories
are
available
if
dimming
is
objectionable,
eNote
-
do not add
additional
start
assists
to units already having
a
factory-installed
start
assist.
VC,lUffOU -
Three-phase
units must
be
wired
properly
to
ensure
proper
compressor
rotation. Improper rotation
may result
in
compressor damage.
An
electronic
phase
sequence
indicator
must
be
used
to
check supply-wiring
phases.
Also, the
"Wild" leg of
the
three-phase
power
must
be connected
to
the
middle
leg
on the
contactor'
Important
-
Only
the
ECONAR
PumpPAKrM is
certified
to
be
wired directly to the
compressor contactor and
can
be
grounded
in
the
grounding
lug
for
208l23oYac. An
alternative
loop
pump
or a
pump
for
a
different
supply
voltage must
be
powered
from
a
separate
fused
power
supply
and
confrolled through
an
isolation relay that
has
its coil
wired to
the
contactor
circuit.
An
intemal pump
relay provides the electrical
power
through
the 3-pole terminal
block
(BP)
for
the
hydronic-
side circulator pump.
The
use
of
impedance
protected
i0
pumps
eliminates the
need
for
additional fusing.
Do
not
connect more than
a
1/3
horsepower pump
to
the
internal
pump
relay
terminal
block.
eNote
-
The
GW380
does
not have
an
internal
pump relay.
A
pump
for
the GW380,
or
a
pump larger than
1/3 horsepower
on any
other
unit,
must be powered
from
a
separate
fused
power
supply
and
controlled through an isolation
relay
that has
its
24Vac
coil
wired to
the
Y
and
X
terminals.
V[I.
}4YOLT
CONTROL CIRCUIT
Note
-
Always refer
to
the inside
of
the
electrical box
cover
for
the
correct
wiring
diagram.
There
are three
basic
sections
of
the
low
voltage circuit;
transformer, remote
hydronic
controls,
and
controller.
A. Transformer
An
internal
transformer provides
24Yac
for all
control
features
of
the heat
pump. Even though the transformer is
larger than
the
industry
standard,
it
is
in
a
warm
electrical
box
and can
be
overloaded
quickly. Table
5
shows
the
transformer
usage
for
the
hydronic
heat pumps.
Table5-TransformerU
elmportant
-
If
the system's extemal conffols
require
more than shown
in
Table 5,
an
extemal
transformer
and
isolation relays should
be
used.
Table
5
shows
that
the
heat
pump's
internal transformer
can
easily power the 24-
Volt
system.
In
conffast, Figure
4
shows
a
fan
coil
system
with its own
power supply,
which
must interface
to
the
heat
pump
to put
the
heat
pump
into
the
cooling
mode.
This can be
accomplished
by
using
the fan
coil's
independent
power supply
to
energize
the
coil
of
an
isolation
relay with
contacts located
in
heat
pump's
conffol circuit.
9WARNING
-
The
GW380
uses a
large-capacity 24Yac
Control
Transformer,
and
freld
wirhg
to
remote
hydronic
controls
must
be suitable
for NEC
Class
1.
elmportant
-
Miswiring
of
24Yac
control
voltage
on
system
controls
can
result
in
transformer bumout.
elmportant
-
Units with
a
dual voltage
rating
(example,
2081230)
are
factory-wired
for
the
higher
voltage
(example, 230).
If
connected
to
a
power supply having the
1
7 (2)
21
4
N/A
Pump Relay
4
8
18
8
Reversing
Valve
2
2
Controller
20-1038
2
Compressor Overload
6 (2)
N/A
N/A
4 (2)
N/A
4
Contactor
Pilot
Relays
2
2
2
10
10
10
1O6VA
33VA
44YA
50
75
150
Transformer
VA
size
f
I
380
29-67
98,120
Component
Remote
Hydronic Control
Plus
Accessory
("A)
Total

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents