Hydronic-Side Heat Exchangers; Temperature Limitations; Tv Unit Location / Mounting; Ground Source Design - Econar GeoSource 2000 GW Series Installation And Operating Instructions Manual

Hydronic
Table of Contents

Advertisement

ground water
systems because
the loop
Entering
Water
Temperature
(EWI)
is
lower. EWT
affects
the
capacity
of
the
unit
in
the
heating
mode, and
loops
in cold
climates
are
normally
sized
to
supply
a
wintertime
EWT
to
the
heat
pump down to
25oF.
2.
Ground Water
Systems
(see
Figure
3)
The design water
tefirperature
will
be
the well
water
temperature
in
the
geographic
region
for
gtound
water
systems.
Typical well
water temperatures
are
in
the
507
range
in
many
cold
climates.
If
well
water temperature is
lower
than
50T
(Canadian
well
water
can
be
as
low
as
40oF),
the
flow
rate must
be
increased
to
avoid
leaving
water
temperatures
below
the
freezing
point.
If
well
water
temperatures
are above
50oF
(Some southem
states
are
above 70oF), the
flow
rates
may
need
to be
increased to
dump energy more
efficiently during
the
cooling
mode.
Varying
well
water temperatures
will
have
little
effect
on
unit
capacity
in
the cooling
mode (since
the well
is
connected
to
the
heat
pump
condenser),
but
can
have
large effects
on
capacity
in
the heating mode
(since
the
well
is
connected
to
the
evaporator).
If
well
water
temperatures exceed 70oF, special considerations such
as
closed
loop
systems
should
be
considered.
C.
Hydronic-Side Heat Exchangers
Hydronic-side heat
exchangers discussed
in
section
VI
are
designed
to
operate
at a specific
fluid
supply
tenperature.
This
operating temperature
will
have
to
be supplied to
the
selected space
conditioning
heat
exchanger
by
the
hydronic heat pump.
The
manufacturers
or
suppliers
of
the hydronic-side heat exchangers
publish
the capacity
of
their
equipment
at different
operating
temperatures
and
fluid flow
rates,
and these
capacities
and
operating
temperatures are
required
to
select
the
heat
pump
to
be
used
in
the
system.
When
selecting
the
heat pump,
choose
a unit that
will
supply the
necessary
heating
or cooling
capacity
at
the
minimum
and maximum hydronic loop
temperature
conditions, respectively. Example;
if
a fan
coil
system
requires 35000
Btuihr
to
cool
a
space
with
45oF water
temperature
entering the water-to-air fan
coil,
a GW42x
GeoSource
2000
heat
pump
is
required
to
handle
the
cooling
load.
lf
an
intermediate heat
exchanger
is
used
between
the
storage
tanks as pictured
in
Figure
1,
expect
a
10oF
operating
temperature
difference
between
the
two
tanks.
For
example,
if
the
direct-coupled storage
tank
is
at
110oF,
expect the
maximum
operating temperature
of
the
indirect-coupled tank
connected
through
an intermediate
heat exchanger
to be
100oF.
D. Temperature
Limitations
Be
aware
of
the
operating
range
of
the geothermal
system
when sizing
the
particular
heat
pump
to
avoid premature
equipment
failure.
Operating
outside
of
these
limitations
may
cause severe damage
to
the equipment and may
void
warranQr.
VCAUTIONS;
-The
acceptable
hydronic
LWT is
70oF
to
115oF
for
heating
and
35oF
to
50oF
for
cooling. Hydronic EWT
should remain
above
50oF
to avoid low-pressure lockouts.
-The
acceptable
Ground
Loop EWT is
25oF
to
50oF
for
heating
and
50T to
100oF
for
cooling.
-The
acceptable
Ground Water
EWT
is
45T
minimum
in
heating and
100oF
maximum in
cooling.
TV. UNIT LOCATION
/
MOUNTING
@Important
-
To
ensure easy
removal
and replacement
of
access
panels, leave
panels
secured
in
place
until
the
unit
is
set
in
place
and
leveled.
qlmportant
-
Locate
*re unit
in
an
indoor
area where
the ambient temperature
will
remain
above
45oF.
Service
is
done
primarily from
the
front. Top
and
rear
access is
desirable
and should be
provided when possible.
elmportant
-
A
field
installed drain pan
is
required
under
the entire
unit
where accidental
water
discharge
could
damage
surrounding
floors,
walls
or
ceilings.
VCAUTION
-
Do
not
use
this
unit
during
construcrion.
Dust and debris
may quickly
contaminate
electrical
and
mechanical components; resulting
in
damage.
VCAUTION
-
Before
driving
screws
into the
cabinet,
check
on the
inside
of
the
unit
to
ensure the
screw
will
not
damage
electrical, water, or
refrigeration
lines.
e-Important
-
Units
must
be
mounted
on
a
vibration-
absorbing
pad
slightly larger than the
base
to
provide
isolation between
the
unit
and
the
floor. Water
supply
pumps should
not be
hard plumbed
directly
to
the unit
with
copper
pipe; this
could transfer
vibration
from
the
water pump
to
the
refrigeration
circuit,
causing
a
resonating
sound.
Hard plumbing must
be
isolated from
building
structures
that could fransfer vibration
from
the
unit
through
the
piping
to
the
living
space.
eCAUTION
-
Always
use
plastic male
fittings
into
plastic
female
or into
metal
female
fittings. Never
use
metal
male
fittings
into plastic female
fittines.
On
metal-
to-metal
fittings;
use
pipe
thread compound,
do not
use
pipe
thread tape, hand
tighten
flrst,
and then
only
tighten
an
additional
Vz
tum
with
a
tool
if
necessary.
On
plastic
fittings,
always
use
2
to 3
wraps
of
pipe
tlread
tape,
do
not
use
pipe
thread
compound, hand tighten
frst,
and then
only tighten
an
additional
7z
turn
with
a
tool
if
necessary.
Do not over-tighten, or
damage
may occur.
V.
GROUND SOURCE DESIGN
Since water
is the
source
of
energy
in
the
winter
and
the
energy
sink
in
the
summer,
a
good water supply
is
possibly the
most
important
requirement
of
a geothermal
heat
pump
system
installation.
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents