Building Heat; Transformer - Econar GeoSource Invision 3 Q Series Installation And Operating Instructions Manual

Dual circuit, vertical forced air
Table of Contents

Advertisement

1.
Closed
Loop
Systems
Closed loop
systems
use
a
heat exchanger
of
high density
polyethylene pipe buried underground
to
supply
a
tempered water solution back to
the heat
pump.
Closed
loops
operate
at
higher
flow
rates than open
loops
since
the
entering water temperature
(EWT)
is
lower.
The
loop
EWT
supplied to
the heat
pump
has a
great
effect
on the
capacity
of
the
unit in
the
heating
mode.
Earth loops in
cold climates
are
normally
sized
to
supply
a
wintertime
EWT
to
the heat
pump
from
32oF
down to
25oF,
which
minimizes
the
installation
cost
of
the earth
loop
and
still
maintains proper
system
operation.
The
unit GPM
requirements
and pressure
drops
for
loop pump sizing
is
available in Table
2.
Due to
the
effect
of loop
water temperature
on
heating
capacity in the domestic hot water
(-DHW
and
-DWR)
modes,
a
loop
temperature
restriction
is applied to
these
DHW
applications.
If
earth
loop
temperatures exceed
80oF,
the
DHW
compressor's capacity
will
increase
to
the
point of
overloading
the
DHW
condenser
coil.
This
will
result
in
high-pressure
lockout of
the
DHW
mode.
If
heat
pump installations
are
expected to
reach the
80oF
earth
loop
temperature mark, extra consideration
will
have
to
be
given to
lowering
the head pressure
by reducing earth
loop
flow,
increasing
earth
loop
length, increasing
DHW
loop
flow,
or reducing
DHW
output temperature.
When selecting
the heat
pump,
choose
a
unit
that
will
supply
the necessary
heating or
cooling
capacity
at the
minimum
and
maximum
earth
loop temperature
conditions
respectively.
Example;
if
a
residential
system
requires 60,000
Btu/tr
to
heat
a
house
on
an earth
loop
system (designed
for
32oF
minimum wintertime EWT),
and
40,000
Ba/tr
to cool
the house
on
an earth
loop
(designed
for
70oF
summertime
EV/T),
a
Qi8kW6T
GeoSource
Invisionr
heat
pump
is
required.
2.Open Loop
Systems
On
an
open
loop
system the
design water temperature
will
be the
well
water temporature
in
your geogmphic region.
Many
cold climates
are
in
the
50oF
range
for well
water
temperature.
Flow
rate
requirements
(in GPM)
and
unit
water-side
pressure
drops (in PSI)
at
50oF
EWI
are
available
in
Table
2. If
your
well
water
temperatures are
lower
than
50oF,
for
instance
Canadian
well
water
can be
as
low
as
43oF, the
flow
rate must
be increased
to avoid
leaving water
temperatures
below
the
freezing
point.
If
well
water
temperatures are above 50oF,
as
in
some
southem
states
where
well
water
temperatures are above
70oF, the
flow
rates
may
need
to
be increased
to dump
heat
more
efficiently in
the
cooling
mode.
Varying well
water temperatures
will
have
little
effect on
unit
capacity
in
the
cooling mode
(since the
well
is
connected
to
the heat
pump
condenser),
but
can
have
large effects on
the
capacity
in
the
heating mode (since
the
well
is
connected
to
the
evaporator).
If
well
water
temperatures are
to
exceed 70oF, special
considerations,
such
as
closed
loop
systems, should be addressed'
10
B.
Building
Heat Loss/fleat
Gain
The
space
load
must be
estimated accurately
for
any
successful
HVAC
installation.
There
are
many
guides
or
computer programs available
for
load estimation
includhg fte
ECONAR
GeoSource
Heat Pump
Handbook, Manual
J, and
others.
After
the heat loss/heat
gain is completed
and
loop
EWT
are established, the heat
pump
can
now be
selected
using the specifications
data.
Choose the
capacity
of
the heat
pump
based on
both
heating
and
cooling
load.
VII.
ELECTRICAL
SERVICE
The main electrical service
must be
protected
by
a
fuse
or
circuit
breaker,
and be capable
of providing
the amperes
required by
the
unit
at
nameplate
voltage.
All
wiring
shall
comply with
the
national electrical
code
and/or
any
local
codes
that may
apply.
Access
to
the
line
voltage
contactor is
gained
through
the
knockouts provided on
either
side
of
the heat
pump next to
the
front
corner.
Route
EMT
or
flexible
conduit
with
appropriate 3-
conductor
wire
to
the
contactor.
9WARNING
-
The
unit
must
be
nroperlv erounded!9
When supplying power to external water pumps
with
the
heat
pump's power supply,
use
only
impedance protected
motors. ECONAR
PumpPAKsrM
can be
wired
directly
to
the
contactor
in
the
electrical
box.
The relay
will
energize
the
PumpPAKrM
with
a
call for
heating or
cooling.
The
use
of
impedance
protected pumps eliminates
the need
for
additional
fusing
on the
PumpPAKrM.
VIII.}4YOLT
CONTROL
CIRCUIT
The
wiring
diagrams
in
Figures 7
and 8
show
the
low
voltage controls
of
the heat
pump. This
section
will
break
down
the three
basic components
of
the
low
voltage
circuit;
transformer, thermostat,
and
controller.
A. Transformer
Electrical
diagrams
are
provided in Figures 7 and
8, and
on the
electrical box cover panel
of
the heat
pump. An
internal 24-volt,75
VA
transformer
is
provided to
operate
all
control features
of
the heat
pump.
Even though
these
ffansformers
are
larger
than the
industry
standard
40
VA
ffansformer, they
can
still
be
overloaded
quickly
when
using
it for control
equipment
like
zone
valves.
Table
3
shows the
transformer
usage
for
GeoSource
Invision3
heat pumps.
If
any system's extemal controls require more
than
the
VA
available
for
external
use
from
the transformer,
a
separate
transformer
must be used.
The
heat
pump's
transformer
can
generally power simple external
control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents