Hydronic-Side System Design - Econar GeoSource 2000 GW Series Installation And Operating Instructions Manual

Hydronic
Table of Contents

Advertisement

8.
Stop the pump, and
let
the
solution
stand
for
about
15
minutes.
9.
Flush the solution
by
adding
a
fresh water supply
to
the
pail.
Flush
until
the
leaving
water
is
c1ear.
Note
-
observe
local
codes
for
disposal.
10.
Flush
the
entire
heat
pump
system
with
water.
VI.
HYDRONIC.SIDE SYSTEM
DESTGN
This
section deals
with
some
common
practices
used
when coupling
the
ECONAR
GeoSource
2fi)0
hydronic
heat pumps
to
the
space
conditioning
heat
exchanger.
There are
so many
possible applications
for
hydronic
systems
that they cannot
all
be
covered
in
this
text.
Hopefully
these ideas
can
help
in
many
of
your
system
designs.
eNote
-
Actual
systems
must be constructed to
all
appropriate
codes and
according
to
accepted
plumbing
practices.
Always
use
copper pipe
on the
hydronic
side.
elmportant
-
Pressure/Temperature
ports
!gu!.!!
be
installed
in
the entering and
leaving hydronic lines
of
the
heat
pump.
A.
Storage Tanks
@Important
-
The
heat
pump must
be
coupled
to
the
space
conditioning
system
through
a
water
storage
tank.
elmportant
-
The guideline
for
the
total
fluid
storage
in
the system
is
l0
gallons
of
fluid for
each
ton
of
hydronic
heat
pump capacity
(example,
50
gallons
minimum
for
a
5-ton
unit). Size the
stora-qe
tank
for
the
diflerence
between the amount
of
fluid
in
the smallest
hydronic loop
and what the
system
requires.
If
in
doubt, size the
storage
tank
for
the
total
capacity
of
the
heat
pump.
A
properly
sized
storage
tank
eliminates
many problems
with
multiple
zone
hydronic
systems. These problems include
excessive
leaving water
temperature
if
a
single
zone
cannot dissipate heat
quickly
enough, and
hydronic
flow
reduction through
the heat
pump when
only
one zone is
calling.
This
may occur
because
the
hydronic circulating
pump
is
normally sized
to
provide
the
heat
pump's
required
flow with all
zones
calling.
In
applications that
use
multiple smaller
zones, storage
tanks
absorb
the
relatively
large amount
of
energy supplied
by
the
heat
pump
in
order
to
provide longer
run
times and
less
compressor
cycling
for
the heat
pump.
Storage
tanks
also
serve
to
dispense
energy
in
small
amounts
so that
the
conditioned zones have
time
to
absorb
heat
without
requiring high
discharge
water
temperatures.
(The
only
instance where a
storage
tanks
is
not required
is
when
the
heat
pump is coupled
to
a
large
heat
exchanger containing
the
recommended
amount
of fluid
capable
of
absorbing
the
entire capacity
of
the heat
pump.)
Insulated
water
heaters
are commonly
used
for
storage
tanks.
aNote
-
Always
check local
codes
to
ensure
water
heaters
can be
used as storage tanks.
Using
the
electric
elements
in
the
tank
as
a secondary heat source
to
the heat
pump
is
appealing
in
some
applications,
but
special
8
Listing
Agency Certifications may be required
by
many
local
codes.
Specially
listed
water
heaters
are
available.
While
all hot
water tanks are insulated
on
the
top
and
sides, many
do not
have insulation
on the
bottom. An
insulated
pad
beneath
uninsulated
tanks
will
reduce
energy
loss to
the
floor.
@Important
-
The hydronic
flow
into
the
storage tank
(particularly
a water heater) must
not
be restricted.
If
the
water heater
has
an
internal diffuser
"dip
tube," cut
it
off
at
approximately
l2
inches
into
the tank.
The tank
temperafure
can
be conffolled
with a
simple
Aquastat
or
a
setpoint
controller. The
setpoint
controller
senses
tank water temperature
and
outside
air
temperature
to
increase
the tank
temperature
as the
outside
air
becomes
colder.
This control
scheme
provides
the
highest
heating efficiencies
by requiring
the
lowest possible water
temperature
to
heat
the
space.
Setting the
optimal
design
temperatures
in
the
conlroller
is
difficult,
and
the
simple
Aquastat
does
have
its
advantages.
To
help
in
setpoint
control,
the
following
equation
can
be used:
Reset
Ratio
=
Design Water Temp
-
Indoor
Design Temp
Indoor
Design Temp
-
Outdoor Design Temp
B.
Hydronic
Side
Circulators
Hydronic circulator
pumps transfer
the
energy
supplied
by
ECONAR's hydronic heat pumps
to
the
space
conditioning heat
exchanger.
Select
a
quiet
operating
pump
with
the
ability to
supply
the
required
flow
rate
at
the
system pressure
drop. The circulator
supplying
the
heat
pump must
be
placed
in
the
water supply
line into
the
unit to
provide the
best
pump
performance. Individual
zone
circulators
must
also be
placed
in
the supply lines
of
the heat
exchangers
they
serve. These
pumps are
often
used as
the
on/off control
mechanism
for
the
zone they
supply
as
shown
in
Figure
4.
Zone valves are
also
commonly
used
for
this
purpose
using a
corrrmon pump
(shown
in
Figure
5).
eNote
-
Select a common
pump at the total
flow of
all
the
zones
and the highest
pressure
drop
of
any
one
parallel
zone. Small Grundfos pumps (230
Vac)
should
be
used as
circulator
pumps. These pumps are
impedance
protected and do
not
require
additional fusing
if
powered
directly from
the
heat
pump.
VCAUTION
-
Never
operate
with
hydronic
flow
rates
less
than specified.
Low
flow
rates,
or
no
flow,
may
cause
the
unit
to
shut
down
on
a pressure
lockout or
may
cause
a freeze
rupture
of
the heat exchanger.
Pumps
must
be
sized
to provide
the required
flow to
a
heat
exchanger
at
its
corresponding pressure
drop.
This
pressure
drop
can
be
calculated
from the total
pressure
drop
through
the piping, plus the
pressure
drop
of
the
space
conditioning
heat exchanger, and
plus
the
pressure
drop through the
heat
pump heat
exchanger.
Table
4
shows the
hydronic water-flow
requirements
and pressure
drop (dP),
and
Table 3
shows the dP
multiplier for
various
I

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents