Controller - Econar GeoSource 2000 GW Series Installation And Operating Instructions Manual

Hydronic
Table of Contents

Advertisement

lower
voltage,
change
the wiring
to
the
transformer
primary to
the correct lead; otherwise
premature
failure,
or
inability
to
operate the
control
components may occur'
B. Remote
Hydronic Controls
The GW29-67
heat
pump
series uses a
single-compressor,
and
the GW98, GW120 and
GW380
use
a
[andem
compressor
(two
compressors connected
together).
The
GW98,
120,
or 380
can be
ordered either as;
1)
controlled
as
one
system
with a
single
Y
input
with
an
adjustable
time
delay
for
the
2od
compressor contactor,
or 2)
stage-
controlled
with
separate
Y
and
Y2
inputs
with
an
adjustable
time delay
for
the Y2-controlled
contactor.
Consult
the
instructions packaged
with the
remote
hydronic
conffols
for
proper
mounting
and
operation-
Vlmportant
-
If
one remote hydronic
control
operates
multiple
heat
pumps,
the
conffol
wiring
of
the heat
pumps
must
be
isolated
with
isolation
relays
to
avoid
excessive
voltages
or
overheating
and
premature
failure
of
the
conftol
compononts.
Power
is
supplied
to
the
remote
hydronic control from
the
R
and
X
terminals
on the heat
pump
terminal
strip.
A
single-stage
hydronic control
(heating Aquastat)
on
a
storage
tank
or
a
wall
mounted thermostat may be
a1l
that
is
required
for
simple heat-only
systems.
The
contact
on
the
hydronic control
closes and
provides 24Vac to
the
Y
terminal.
When using
a
hydronic control, insert
the
temperature sensor
approximately 1/3
of
the way
down
into
the storage
tank.
Set
the
hydronic control
setpoint to
1
l0-1
15"F
typical,
and set the
differential
to
15oF
to avoid
short
cycling.
eCAUTION
-
The setpoint
of
the
hydronic conffol
must
limit
the
LWT from
the
heat
pump
to
a
maximum
of
120oF
to avoid premature
failure of
the compressor.
A
cooling hydronic control
(Aquastat)
can
be mounted on
the
water supply
line,
as
shown
in
Figure 4. This control
acts
as
a
1ow
limit,
which
shuts the heat
pump down when
the
cooling
water
reaches
the setpoint
(e.g.
45"F).
Changeover
from
heating
to
cooling
can
be
achieved
in
two ways:
1)
a
manual
toggle switch to
select the heating
or the cooling
hydronic control
(Aquastat),
or 2)
a
cooling
thermostat
which
powers the
coil
of
a
single pole/double
throw relay
to
select
the
heating hydronic
control
(normally
closed contact)
or
the
cooling hydronic control
(normally
open
contact).
eNote
-
Always
wire the
system
to
shut
down (Anti-
short-cycle)
between
a
heatiag
and cooling
mode
changeover,
or
nuisance
trip-outs
could occur
from
changing
modes
"on
the
fly".
For
Zoning
applications,
any
number
or
rypes
of
thermostats, Aquastats,
or
switches can
be
used
with
an
independent
power supply (typically
a
24-volt
transformer) to activate specific
zone
controls.
These zone
controls are
normally
either
a
zone
pump (Figure
4)
or
zone
valves (Figure 5). End
switches
on the
zone valves
can
be
used
to control
a
pump
relay
when the zone valve
is
open.
The
pump
relay then
activates a
coulmon
pump,
which
supplies
any nurnber
of
zones.
Example: the
fan
coil
in
Figure
4
could be
supplied
by
the
same
pump
as
the radiant
floor
system
if
zone
valves
were used
instead
of two
pumps.
C.
Controller
The
controller
receives
a
signal
from
the
thermostat
and
initiates
the
correct
sequence
ofoperation for
the
heat
pump. The
conffoller
performs
the
following
functions:
1)
Compressor
Anti-Short Cycle
2)
Compressor
Control
3)
Ground Loop Pump
/
Ground Water
Initiation
4)
Compressor Staging
5)
Hydronic Circulator
Pump
Conffol
6)
4-Way Valve Control
7)
Compressorl,ockouts
8)
System
Diagnostics
9)
24Vac
Fuse
10)
Plug Accessory
11)
AlarmOuput
1.
Compressor
Anti-Short
Cycle
An
anti-short-cycle
is
a delay period
between
the
time
a
compressor
shuts
down
and
when
it
is allowed
to
come
on
again.
This
protects
the
compressor and
avoids
nuisance
lockout
conditions
for
these
two
conditions;
1.
A
70
to
130-second
random time-out
period
occurs
before
a
re-start after
the
last shutdown.
2-
A
4-minute/25-second
to
4-sinutel45-second
random-
start
delay
occurs
immediately after power
is
applied
to the
heat
pump.
This
occurs
only
after
reapplying
power
to
the unit.
To
blpass
this timeout
while
servicing
the unit,
apply power,
disconnect
and
reapply power very
quickly to
shorten
the delay.
2.
Compressor Control
When 24Vac
is
applied
to
the
Y
terminal on the
wiring
terminal
block,
the
controller
then
decides, based
on
lockout
and anti-short-cycle periods, when
to bring
the
eompressor on. The
Ml
output
of
the
controller
energizes
the
compressor
contactor, and
the
compressor stays on
until
the
24Yacis
removed
from
the
Y termhal.
3.
Ground Loop Pump / Ground Water
Initiation
On
ground
loop
systems, a
Ml
output
from
the
controller
will
energize
the contactor, starting the
compressor
and
the ground loop pump. On ground water
systems,
a M1
output
from
the
controller
will
energize the ground water
solenoid valve through
the "P1ug
Accessory" connector.
4.
Compressor Staging
GW98, GW120,
and
GW380
can be ordered
with
staged
compressors
controlled
with
separate
Y
and
Y2
inputs.
The
Mi
output
of
the controller
energizes
the
flrst
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents