Z4Yolt Control Circuit; Transformer - Econar GeoSource 2000 GV Series Installation And Operating Instructions Manual

Vertical and horizontal forced air
Table of Contents

Advertisement

L
the
PumpPAKrM
with
a
call for
heating or
cooling.
The
use
of
impedance
protected pumps eliminates
the need
for
additional
fusing
on
the
PumpPAKrM.
VIII.
}AYOLT
CONTROL
CIRCUIT
The
wiring
diagrams in Figures 5
and
6
shows the
low
voltage controls
of
the heat
pump. This
section
will
break
down
the three
basic components
of
the
low
voltage
circuit;
transformer, thermostat,
and
controller.
A. Transformer
Electrical
diagrams
are
provided in Figures
5 and
6
and
on
the
electrical box cover panel
of
the
GeoSource
20(X)
heat
pump. An internal
24-volt,55 VA
transformer
is
provided to
operate
all control
features
of
the heat
pump.
Table 4
shows the
transformer
usase
for
GeoSource 2000
heat pumps.
Table
4
-
Transformer
If
any system's external controls require more than
the
VA
available
for
external
use
from
the
transformer,
a
separate
transformer
must
be
used.
The
heat
pump's
transformer
can
generally power simple external control
systems
consisting
of
a
few
relays or
a zone
valve
(depending,
of
course,
on
the
VA
draw
of
the
components).
On more complicated
control
systems the
transformers capacity is
used
up very
quickly.
cNote:
For units operating on 208V
electrical
service,
the
transformer
must be
switched to
the
correct lead
(see
electrical diagram
-
Figures 5
and
6).
Units
are
factory
shipped
with
the
transformer
set
for 240V
service.
Operating
a
unit
on
208V with
the
transformer
set
to
240V
will
cause
the
unit
to
operate
with lower
than
normal
control
voltages.
B. Thermostat
A2-heatll-cool
thermostat is recommended
for
proper
operation
of
GeoSource
2fi)0
heat
pumps. Eight wire
thermostat cable
is
required
for
proper operation
of
the
thermostat.
Consult
the
instructions
in
the
thermostat box
for
proper mounting
and
thermostat operation.
V
C.LUffON-
miswiring of control
voltage on
system
controls
can
result
in
fuse
or
transformer burnout.
eNote:
If
a
single thermostat controls
multiple
heat
pumps,
the
control wiring of
the heat
pumps
must be
isolated
from
each
other. This
will
prevent
the heat
pumps
from
receiving
high
voltage through
the
common
wiring
if it
is tumed
off
at the
circuit
breaker
for
service.
Power
is
supplied to
the
thermostat by connecting
the
R
and
X
terminals to
the heat
pump
terminal
strip.
The
fan
is
controlled
through
the
G
terminal
and
will
operate
continuously in
the
FAN ON position or
when
the
compressor
is
running
in
the
FAN
AI-ftO position.
The
Y
terminal
energizes the
compressor. The
unit
is
put
into
the
air
conditioning
mode when
the
thermostat
energizes
the
O terminal,
which
operates the
4-way
reversing valve.
A
lockout condition
is
indicated by
the
L
terminal,
which
lights
a
red
light
on
the
thermostat (depending
on the
thermostat). This
lockout
condition
means
that
the
unit
has shut
itself
down on
a
low
or high-pressure switch
to
protect
itself,
and
will
not
come
back
on
until
power
has
been reset
to
the heat
pump.
If
a
lockout condition
exists,
the heat
pump should not
be reset
more
than
once.
A
service technician should
be
called immediately.
Repeated reset can
cause dama-ee
to
the system.
If
second stage
heating
(e.g.
electronic
resistance
strip
heat) is
used,
its control wiring
is
connected
to
X
and
W2
on the heat
pump
terminal
strip.
Fan
interlock
relays
are
not required
since the
thermostat
energizes the
blower
whenever the
second stage
is
calling.
W2
on
the
terminal
strip is wired
directly to
second
stage
heating
on the
thermostat. In
the event
of
a
heat
pump shutdown,
switching
the
thermostat to emergency
heat energizes the
E terminal,
which
runs
the
blower
and second
stage
heater
but
does
not
energize the
compressor. The thermostat
will
indicate whenever
second stage
heating is
energized.
These
wiring
connections
are
listed in Table
5.
Table
5
-
Connections
Use
of
a
programmable
setback
thermostat
in
conjunction
with
a
geothermal
heat
pump
and
a
second
stage
backup
electric
resistance heater
has
the
potential to
cause
inefficiency.
The energy savings supplied by
ni-eht
setback
could
be less
than
the
energy
used
by
the
electric
elements
if
they
operate
in
the
moming
to warm
the space
to
the
daytime temperature
setting.
Second stage usage
should be
monitored and
setbacks
adjusted to maximize
energy savings
of
the
entire
system.
eNote: If
the
thermostat
is
provided by
others and is
equipped
with
an
anticipator,
it
should
be
set
to its highest
setting to avoid
interfering with
heat
pump operation.
9
Contactor
1
7
x2
4-Way Valve
4
4
Controller
')
2
Thermostat
I
1
Blower
Relay
6
6x2
Electric
Heat Relay
(optional)
6
NA
Total
26
JJ
Available
29
22
R
R
24
Volt
Power
Common
x
c(x)
Blower
G
G
Reversing
Valve
o
o
1"
Stase
Heat/Cool
Y1
YI
Lockout
Sisnal
L
L
2oo
Stage
Heat
w2
w2
Emergency Heat
E
E
\
L
Comoonent
18{7
98-12{'
Functiog
Terminal
Strip
Tlrermostat

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents