General Network Outputs - Honeywell TC500A Integration Manual

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

General network outputs

Name
no_LocalOccSensState
no_EffOccSensState
no_EffOccState
no_ManualOverride
no_BypassState
no_BypassValue
no_OccupancyState
no_SmokeMode
no_SystemDisable
no_ServiceMd
no_EffDlcShift
no_EffHeatSp
58
Table 29:
Default
Range
Value
1=Occupied
3=Unused
2=Unoccupied
3=Unused
1=Occupied
3=Unused
2=Unoccupied
3=Unused
1=Occupied
5 = Null
2=Unoccupied
3=Bypass
4=Standby
5=Null
1=Occupied
5=Null
2=Unoccupied
3=Bypass
4=Standby
5=Null
0=No Bypass
No Bypass
1=Bypass
(0)
0-100
Null
0=Unoccupied
Unoccupie
1= Occupied
d (0)
1=No Override
1=No
2=Shutdown
Override
3=Pressurize
4=Depressuriz
e
0=Normal
Normal (0)
1=Disable
0=Disable
Disable (0)
1=Enable
0-10 Deg F
Null
40-120 Deg F
Null
General network outputs
BACnet
Point Type
BACnet
ENUM Value
BACnet
ENUM Value
BACnet
ENUM Value
BACnet
ENUM Value
BACnet
Boolean
Output
BACnet
Numeric
Output
BACnet
Boolean
Output
BACnet
ENUM Value
BACnet
Boolean
Output
BACnet
Boolean
Output
BACnet
Numeric
Output
BACnet
Numeric
Output
BACnet
Object
Description
Instance
ID
1
Local Occupancy sensor
state
2
Effective Occupancy sensor
state
20
Effective occupancy state.
4
Manual Override
1
Bypass State Output
1
Bypass Value output. 0=No
Bypass, 100=Bypass.
3
System is in occupied/
unoccupied state.
5
Current smoke mode state.
4
System disable.
5
Service mode enable
2
Effective Demand Limit Shift.
3
Effective Heating Setpoint