Recovery setpoint configuration

Key
Cfg_Recovery_MaxCoolRampRate
Cfg_Recovery_MinCoolRampRate
Cfg_Recovery_MaxCoolRampTemp
Cfg_Recovery_MinCoolRampTemp
Cfg_Recovery_MaxHeatRampRate
Cfg_Recovery_MinHeatRampRate
Cfg_Recovery_MaxHeatRampTemp
Cfg_Recovery_MinHeatRampTemp
Recovery setpoint configuration
Table 18:
Recovery setpoint configuration
Options /
Default
Range
Value
Δ
Δ
0 to 20
°F/
6
°F/hr
hr
Δ
Δ
0 to 20
°F/
2
°F/hr
hr
-40 to 120
70 °F
°F
-40 to 120
90 °F
°F
Δ
Δ
0 to 36
°F/
8
°F/hr
hr
Δ
Δ
0 to 36
°F/
2
°F/hr
hr
-40 to 120
60 °F
°F
-40 to 120
0 °F
°F
BACnet
BACnet
Object
Point
Instance
Type
ID
BACnet
18
Numeric
Value
BACnet
16
Numeric
Value
BACnet
17
Numeric
Value
BACnet
15
Numeric
Value
BACnet
22
Numeric
Value
BACnet
20
Numeric
Value
BACnet
21
Numeric
Value
BACnet
19
Numeric
Value
Description
Maximum Cooling
Setpoint Ramp
Minimum Cooling
Setpoint Ramp
Outdoor air
temperature at the
maximum cool setpoint
ramp.
Outdoor air
temperature at the
minimum cool setpoint
ramp.
Maximum Cooling
Setpoint Ramp
Minimum Cooling
Setpoint Ramp
Outdoor air
temperature at the
maximum heat setpoint
ramp.
Outdoor air
temperature at the
minimum heat setpoint
ramp.
35