Heat Pump Configuration - Honeywell TC500A Integration Manual

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Heat pump configuration

Name
Cfg_HeatPmp_CngOv
rRelayType
Cfg_HeatPmp_AuxHe
atLockoutSp
Cfg_HeatPmp_CompL
ockoutSp
Cfg_HeatPmp_AuxHe
atDroop
Cfg_HeatPmp_AuxHe
atRampFactor
Cfg_HeatPmp_Comfo
rtMode
Cfg_HeatPmp_UpStg
Tmr
Heat pump configuration
Table 11:
Default
Range
Value
0 = EnergOnCool
ActiveOn
1 = EnergOnHeat
(0)
30F~120F
65°F
0F~70F
30°F
0 to 10°F
1°F
0.0 to 100.0
2
0 = Saving
0 (Savings)
1 = Comfort
30~960 Mins
0 Mins
(Disabled)
Heat pump configuration
BACnet
BACnet
Object
Point
Instance
Type
BACnet
13
Boolean
Value
BACnet
50
Numeric
Value
BACnet
51
Numeric
Value
BACnet
52
Numeric
Value
BACnet
53
Numeric
Value
BACnet
14
Boolean
Value
BACnet
215
Numeric
Value
Description
ID
Heat Pump Change Over Relay
- Energize on Cooling (O)
- Energize on Heating (B)
Auxiliary OAT High Heat Lockout
Heat Pump Compressor OAT
Low Lockout
Auxiliary Heating Droop
Auxiliary Heating Recovery
Ramp Factor. The heat pump
setpoint recovery ramp is
multiplied by this factor to
determine the auxiliary setpoint
recovery ramp.
Decides the Auxiliary and
compressor Heating operation
Up stage timer value.
27