Honeywell TC500A Integration Manual page 40

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Sylk
Name
Address
10
Cfg_SylkCalOffset_Syl
kBus10Temp
10
Cfg_SylkCalOffset_Syl
kBus10RH
11
Cfg_SylkCalOffset_Syl
kBus11Temp
NA
Cfg_UISensCalOffset_
DATemp
NA
Cfg_UISensCalOffset_
OATemp
NA
Cfg_UISensCalOffset_
MATemp
NA
Cfg_UISensCalOffset_
CO2Lvl
40
Table 21:
Sylk calibration configuration
Range
-10F~10F
-10% RH
~10% RH
-10F~10F
-10F~10F
-10F~10F
-10F~10F
-100PPM
~100PPM
(Continued)
BACnet
Default
Point
Value
Type
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
0
BACnet
Numeric
Value
BACnet
Object
Description
Instance
ID
31
C7400S Discharge Air
Temperature calibration
offset
32
C7400S Discharge Air
Humidity calibration
offset
138
C7400S Mixed Air
Temperature calibration
offset
185
Universal Input Discharge
Air Temperature
calibration offset
186
Universal Input Outdoor
Air Temperature
calibration offset
187
Universal Input Mixed Air
Temperature calibration
offset
188
Universal Input CO2
calibration offset
Sylk calibration configuration