Network outputs

Name
no_CoolCtrl_RunTimeAccumulate
no_LocalOccSensState
no_AuxHeatTermLdOut
no_EffOccState
no_CoolStg1_RunTimeAccumulate
no_HeatCtrl_RunTimeAccumulate
no_HeatStg1_RunTimeAccumulate
no_Fan_RunTimeAccumulate
no_OccupancyState
no_DaHilimit
no_IsHeatDisable
no_IsFanOnly
no_EffSp
no_EffTempMode
no_SystemDisable
no_DehumActive
no_BypassState
42
Table 10 Network outputs
BACnet
BACnet
Object
Object
Type
Instance
Analog
2026
Value
Multistate
2013
Value
Analog
2027
Value
Multistate
2014
Value
Analog
2028
Value
Analog
2029
Value
Analog
2030
Value
Analog
2031
Value
Binary
2015
Value
Binary
2016
Value
Binary
2018
Value
Binary
2019
Value
Analog
2032
Value
Multistate
2015
Value
Binary
2020
Value
Binary
2021
Value
Binary
2022
Value
Range
0 to 270737 hours
enum{Occupied=1,
Unoccupied=2,
Unused=3}
-200 to 0%. Default
is 0%
enum{Occupied=1,
Unoccupied=2,
Bypass=3,
Standby=4}
0 to 270737 hours
0 to 270737 hours
0 to 270737 hours
0 to 270737 hours
Unoccupied=0,
Occupied=1
Off=0,
On=1
Off=0,
On=1
Off=0,
On=1
40 to 120 °F
enum{
CoolMode=1,
ReheatMode=2,
HeatMode=3,
EmergencyHeat=4,
Off=5,
Ventilation=6}
Off=0,
On=1
Inactive=0,
Active=1
NoBypass=0,
Bypass=1
Description
Outputs the actual run time
of cooling control.
Local occupancy sensor
state.
Terminal load for auxiliary
heat.
Effective occupancy state.
Outputs the actual run time
of cooling stage 1
Outputs the actual run time
of heating control.
Outputs the actual run time
of heating stage 1
Outputs the actual run time
of Fan.
System is in occupied/
unoccupied state.
Discharge Air High Limit
output: DAT heating lockout
flag
Heating enabled/ disabled.
Fan only mode enabled/
disabled.
Effective setpoint
Effective temperature mode
System disable.
Dehumidification Active/
Inactive
Bypass state output
Network outputs