38AJ/AZ 046
Do not obstruct
Floor mounting
•
For unit mounting holes, weight distribution and centre of gravity coordinates, refer to the dimensional
drawings supplied with the unit.
•
These units are designed for outdoor installation.
CAUTION:
•
Ensure the air flow around the unit is not obstructed.
•
At least two sides of the units must be free from obstructions, to ensure proper air flow.
•
If several units are installed, next to each other, ensure that the space in between the units is the same as the
unit depth.
•
There must not be any roof or cover above the unit.
Dimensions and clearances
38AJ/AZ 062-074
Do not obstruct
5