Carrier 38AYC Product Data
Carrier 38AYC Product Data

Carrier 38AYC Product Data

(60 hz) heat pump sizes 018 thru 060
Hide thumbs Also See for 38AYC:

Advertisement

Copyright 1997 Carrier Corporation
Product
Data
38AYC (60 Hz)
Heat Pump
Sizes 018 thru 060
The 38AYC Split-System Heat
Pumps are designed for quiet, reliable
heating during the winter and cooling
during the summer. With SEER ratings
from 11.0 to 13.5 and HSPF ratings
from 7.2 to 8.3, these heat pump
systems provide economy of operation
through energy conservation. They
recover heat for indoor comfort from
outdoor air during the heating season
and, by automatically reversing the
refrigerant system, remove indoor heat
and excess humidity during the cooling
season. All models are listed with UL,
c-UL, CEC, CSA-EEV, and ARI.
FEATURES/BENEFITS
Electrical Range — All units are
offered in single phase 208–230v.
Size Range — 38AYC is available in 7
nominal sizes from 018 through 060 to
meet the needs of residential and light
commercial applications.
Compressor — This unit features a
scroll compressor (except 018 size)
which is significantly more efficient
than conventional compressors. Its
simple design offers improved
reliability. Each compressor is
mounted on rubber isolators for
additional sound reduction. For
improved serviceability, the 018
through 042 models are equipped with
a compressor terminal plug.
Continuous operation is approved
down to –30 F (–34.4 C) in the
heating mode and down to 55 F
(12.8 C) in the cooling mode. (See
heating and cooling performance
tables.)
Built-in-Reliable Components —
Includes a suction-tube accumulator
that reduces the amount of liquid
Form 38AYC-1PD

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 38AYC

  • Page 1 CEC, CSA-EEV, and ARI. FEATURES/BENEFITS Electrical Range — All units are offered in single phase 208–230v. Size Range — 38AYC is available in 7 nominal sizes from 018 through 060 to meet the needs of residential and light commercial applications.
  • Page 2: Model Number Nomenclature

    The defrost control is a time/ service valves are brass, front seating temperature initiation/termination All screws on cabinet exterior are type. The 38AYC has sweat field control which includes 3 field- coated for a long-lasting, rust-resistant, connections. Valves are externally selectable time periods of 30, 50, quality appearance.
  • Page 3: Physical Data

    ® CERTIFICATION OF MANUFACTURING SITE. CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI. As an ENERGY STAR Partner, Carrier Corporation has determined that this product meets the ENERGY STAR guidelines for energy efficiency. Physical data UNIT SIZE...
  • Page 4 Accessories ORDERING NUMBER DESCRIPTION KAATD0101TDR Time-Delay Relay — All Sizes P251-0083 (RCD) * Low-Ambient Controller — All Sizes 32LT660004‡ MotorMaster® Control — All Sizes HC34GE231 Ball Bearing Fan Motor — Size 018 HC38GE230 Ball Bearing Fan Motor — Sizes 024–048 HC40GE230 Ball Bearing Fan Motor —...
  • Page 5: Accessory Usage Guideline

    Accessory usage guideline REQUIRED FOR REQUIRED FOR REQUIRED FOR REQUIRED FOR LOW-AMBIENT LONG-LINE BURIED LINE SEA COAST APPLICATIONS APPLICATIONS* APPLICATIONS† APPLICATIONS ACCESSORY (Below 55 F) (Over 50 Ft) (Over 3 Ft) (Within 2 Miles) Crankcase Heater Evaporator Freeze Thermostat Accumulator Compressor Start Assist Capacitor and Relay Low-Ambient Controller...
  • Page 6 Accessory description and usage (Listed alphabetically) continued 11. Liquid Solenoid Valve (LSV) An electrically operated bi-flow shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. NOTE: Compressor Start Assist-Capacitor and Relay must also be used.
  • Page 7: Electrical Data

    Electrical data MAX FUSE† OPER VOLTS* COMPRESSOR MIN WIRE LENGTH OR HACR UNIT VOLTS/PH SIZE (FT) TYPE CKT SIZE 60 HZ 60 C/75 C** 60 C/75 C‡ BKR AMPS 48.0 11.1 14/14 71/66 56.0 11.5 15.5 14/14 53/50 72.5 14.3 19.0 14/14 41/39...
  • Page 8 Dimensions...
  • Page 9 BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR A97079...
  • Page 10: Combination Ratings

    Combination ratings ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER High-Temp Low-Temp Factory- UNIT Supplied Seasonal Sound Carrier Furnace or SIZE- INDOOR Enhance- Standard Efficiency Rating Accessory Accessory SERIES UNIT ment Rating HSPF (dBA) TDR‡ TXV** F(A,B)4ANF024† 18,000 11.00 —...
  • Page 11: Combination Ratings Continued

    Combination ratings continued ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER High-Temp Low-Temp Factory- UNIT Supplied Seasonal Sound Carrier Furnace or SIZE- INDOOR Enhance- Standard Efficiency Rating Accessory Accessory SERIES UNIT ment Rating HSPF (dBA) TDR‡ TXV** CC5A/CD5A/CD5BA030 27,800 NONE —...
  • Page 12 Combination ratings continued ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER High-Temp Low-Temp Factory- UNIT Supplied Seasonal Sound Carrier Furnace or SIZE- INDOOR Enhance- Standard Efficiency Rating Accessory Accessory SERIES UNIT ment Rating HSPF (dBA) TDR‡ TXV** COILS + 58U(H,X)V100-20 FURNACE...
  • Page 13 Combination ratings continued ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER High-Temp Low-Temp Factory- UNIT Supplied Seasonal Sound Carrier Furnace or SIZE- INDOOR Enhance- Standard Efficiency Rating Accessory Accessory SERIES UNIT ment Rating HSPF (dBA) TDR‡ TXV** FK4CNB006 48,000 TDR & TXV 12.50...
  • Page 14 ‡ In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in perfor- mance. Use either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Carrier furnaces are equipped with TDR except for the 58GFA.
  • Page 15: Detailed Cooling Capacities

    Detailed cooling capacities* CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 16 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 17 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 18 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 19 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 20 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 21 Detailed cooling capacities* continued CONDENSER ENTERING AIR TEMPERATURES F EVAPORATOR Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† System System System System System Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡...
  • Page 22: Heat Pump Heating Performance

    Heat pump heating performance OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 23 Heat pump heating performance continued OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 24 Heat pump heating performance continued OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 25 Heat pump heating performance continued OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 26 Heat pump heating performance continued OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 27: System Design

    Heat pump heating performance continued OUTDOOR COIL ENTERING AIR TEMPERATURES F –3 INDOOR Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh† Power MBtuh†...
  • Page 28: Service Training

    Indianapolis, IN 46231 4-97 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book Page 28 Catalog No. 523-887 Printed in U.S.A. PC 101 Form 38AYC-1PD Replaces: 38AYB-3PD 5a 5a...