SiUS042113E
4.19 High Pressure Control in Cooling
F6
Error Code
Method of Error
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
Detection
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
The temperature sensed by the outdoor heat exchanger thermistor rises above A.
Conditions
The error is cleared when the temperature drops below B.
09/12 class
18/24 class
Supposed
Installation space not large enough
Causes
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Part 6 Service Diagnosis
A
(°C)
(°F)
(°C)
62
144
54
61
142
52
B
(°F)
129
126
Troubleshooting
117