Troubleshooting - Trane RTHA Installation, Operation And Maintenance Manual

Solid state starter conversion
Table of Contents

Advertisement

Troubleshooting

Troubleshooting
Table 3.
Troubleshooting chart
Description of the Problem
Chiller starts but only runs for a few seconds.
Compressor starts immediately when power is applied.
Compressor starts, runs less than 10 seconds and
CH530 shuts down on a "Phase Reversal" diagnostic.
While chiller is in "Auto" mode and compressor is off
the shunt trip opens locking out compressor.
Shunt trips opens on compressor start.
See Troubleshooting guides RTHD-SVD02*-EN and RLC-SVD06*-EN for more information.
42
Possible Causes
• Typically caused from a mis-wire of the low voltage.
• Start command of the Benshaw Redistart wired incorrectly directly to 120 Vdc.
• CH530 not programmed correctly. Disable "Phase Reversal" in CH530 controller.
• Troubleshoot the Benshaw SSS using RTHD-SVD02*-EN. Possible problem with SCR.
• P1 setting of Benshaw starter set incorrectly. Remove power to the unit and reprogram
all "P" parameters of the Benshaw starter.
(To program starter, apply external 120V to logic modules.)
(
• Faulty shunt trip.
RLC-SVN005B-EN