T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
FLOAT 1
Fig. 66. Setup - Outputs - Floating Relay - Menu.
SETUP
OUTPUTS
FLOAT 1
ACTUATOR
Fig. 67. Setup - Outputs - Floating Relay - Actuator.
SETUP
OUTPUTS
FLOAT 1
INTEGRAL
Fig. 68. Setup - Outputs - Floating Relay - Integral.
62-0254—13
All manuals and user guides at all-guides.com
2.3.4.1.1. Floating Relay Menu
SETUP
OUTPUTS
The Floating option is only available on the T775B2016,
FLOAT 1
T775B2024, T775B2032, and T775B2040 models.
TYPE
ACTUATOR
When Relay 1 or Relay 3 is setup as floating, relays are
INTEGRAL
paired and the Float 1 or Float 2 menu displays with the
DERIVATIV
SCHEDULE
selections shown in Fig. 66.
RESET
EXIT
M24528
2.3.4.1.1.1. ACTUATOR
SETUP
OUTPUTS
FLOAT 1
The Actuator option displays only on the T775B2016,
ACTUATOR
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.
1. From the menu, use the
90
SEC
2. Press the
3. Use the
ENTER
ACTUATOR
TIMING FOR
FLOAT 1
M24529
4. Press the
The actuator run time is defined as the time needed to
move the actuator from the fully closed to fully open
position and visa versa.
2.3.4.1.1.2. INTEGRAL (
SETUP
OUTPUTS
FLOAT 1
relay only)
INTEGRAL
The Actuator option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.
400
1. From the menu, use the
SEC
2. Press the
ENTER
INTEGRAL
3. Use the
TIME FOR
FLOAT 1
M24530
4. Press the
See Integral NOTES on page 22 for additional information
about setting the Integral time.
28
(floating relay only)
highlight ACTUATOR.
button to display the actuator value.
and
buttons to increase/decrease
the desired number of seconds.
Default: 90 seconds
Range: 0 to 3,600 seconds)
button to accept the value and display
the INTEGRAL option.
modulating/floating
highlight INTEGRAL.
button to display the actuator value.
and
buttons to increase/decrease
the desired number of seconds.
Default: 400 seconds
Range: 0 to 3,600 seconds)
button to accept the value and display
the DERIVATIV option.
and
buttons to
and
buttons to