7.1
Cooling air volume/minimum cross
Fig. 9 a
1
Cool air intake
2
Cool air exhaust
3
Control cabinet cool air intake (L55RS-L75RS only)
The cooling air volume required by these screw
compressors is as follows:
Air-cooled 60 Hz Compressors:
L55, L55RS: 4308 cfm
L75, L80, L75RS: 6003 cfm
Water-cooled 60 Hz Compressors:
Approx. 3531 cfm
If conditions are not favorable, we recommend the
installation of venting ducts. However, the velocity of the
cooling air should not exceed 17ft/sec. We recommend a
minimum duct cross-section of approx. 10 ft
The figures below show the recommended ventilation
sections arrangement:
2
Fig. 9 b
13-25-638 v03
Page 28