Siemens ET 200SP HA Equipment Manual page 38

Table of Contents

Advertisement

Technical specifications
8.1 Technical specifications
Article number
General information
Product type designation
Firmware version
Vendor identification (VendorID)
Device identifier (DeviceID)
Product function
Engineering with
Configuration control
via dataset
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Short-circuit protection
Input current
Current consumption, max.
Inrush current, max.
I²t
Power
Infeed power to the backplane bus
Address area
Address space per module
Hardware configuration
Integrated power supply
Rack
Time stamping
Accuracy
Interfaces
Number of PROFINET interfaces
1. Interface
Interface types
38
I&M data
SPPA-T3000 can be configured/integrated
from version
Address space per module, max.
Modules per rack, max.
Number of ports
integrated switch
6DL1155-6AU00-0EM0
IM 155-6 PN
V1.0
02AH
0309H
Yes; I&M0 to I&M3
V8.0
No
24 V
19.2 V
28.8 V
Yes
Yes
700 mA; +19.2 V to +28.8 V DC
5 A
0.36 A²·s; Due to increased mains buffering of 10
ms
7.5 W; no doubling in redundant mode as the in‐
feed power is also designed as redundant
256 byte
Yes; 24 V DC
56; 56 slots for I/O modules + server module (width
without IM ≤ 1.3 m)
1 ms; In compliance with the supplementary con‐
ditions described in the Equipment Manual
1; 2 ports (switch)
2; via BusAdapter
Yes
Equipment Manual, 09/2021, A5E39262148-AE
IM 155-6 PN HA