Article number
•
•
•
•
•
Potential separation
between PROFINET and all other circuits
between supply and all other circuits
Permissible potential difference
between different circuits
Isolation
Isolation tested with
Ambient conditions
Ambient temperature during operation
•
•
•
•
Dimensions
Width
Height
Depth
Weights
Weight, approx.
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
ERROR LED
MAINT LED
ACT LED
Monitoring of the supply voltage (PWR-LED)
Connection display LINK TX/RX
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
Technical specifications
8.1 Technical specifications
6DL1155-6AU00-0PM0
Yes; red LED
Yes; Yellow LED
Yes; green LED
Yes; green PWR LED
Yes; 2x green link LEDs on BusAdapter
Yes; 1 500 V AC
Yes; Type tested with 1 500 V DC
Safety extra low voltage SELV
1 500 V DC/1 min, type test
-40 °C
70 °C
-40 °C
60 °C
50 mm
138 mm
89 mm
192 g; without BusAdapter
37