Siemens ET 200SP HA Equipment Manual page 36

Table of Contents

Advertisement

Technical specifications
8.1 Technical specifications
Article number
Address space per station
Hardware configuration
Integrated power supply
Rack
Time stamping
Accuracy
Interfaces
Number of PROFINET interfaces
1. Interface
Interface types
Protocols
Interface types
RJ 45 (Ethernet)
Redundancy mode
Media redundancy
Open IE communication
Interrupts/diagnostics/status information
Status indicator
Alarms
Diagnostics function
Diagnostics indication LED
36
Address space per module, max.
Address space per station, max.
Modules per rack, max.
Number of ports
integrated switch
BusAdapter (PROFINET)
PROFINET IO Device
Open IE communication
Media redundancy
Transmission procedure
100 Mbps
Autonegotiation
Autocrossing
– MRP
TCP/IP
SNMP
LLDP
RUN LED
6DL1155-6AU00-0PM0
256 byte
1 440 byte; 1 440 bytes R1 and S1 without CiR,
otherwise 1 000 bytes
Yes; 24 V DC
56; 56 slots for I/O modules + server module (width
without IM ≤ 1.3 m)
1 ms; In compliance with the supplementary con‐
ditions described in the Equipment Manual
1; 2 ports (switch)
2; via BusAdapter
Yes
Yes; Compatible BusAdapters: BA 2x RJ45, BA 2x FC,
BA 2x LC, BA LC/RJ45, BA LC/FC, BA VD
Yes
Yes
Yes; as MRP client
PROFINET with 100 Mbit/s full duplex (100BASE-TX)
Yes; PROFINET with 100 Mbit/s full duplex
(100BASE-TX)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes; green LED
Equipment Manual, 09/2021, A5E39262148-AE