9. Specifications

Permissible temperature ranges
Ambient: -20 ... 70°C [-4 ... 158°F]
Medium: -20 ... 100°C [-4 ... 212°F]
Storage: -20 ... 70°C [-4 ... 158°F]
Ingress protection per IEC/EN 60529
IP30
Process media
Water, ethylene glycol, any other liquid non corrosive to brass, phosphor bronze and
Nitrile material.
Switch point repeatability
±5% of FSR
Switching function
1 × SPDT (single pole double throw)
Silver - alloy contacts, UL certified
Electrical rating
AC rating
Resistive load
Inductive load
125V
250V
125V
250V
15A
15A
15A
15A
WIKA operating instructions, flow switch, model FSM-6100
DC rating
Resistive load
Inductive load
125V
250V
30V
125V
0.5A
0.25A
5A
0.05A
Setting range
Nominal
Paddle
Bore
combinations
in
mm
'L' mm
1
25
28
1.25
32
28
1.5
40
28
37
2
50
37+50
37
2.5
65
37+50
37
3
80
37+50
37+50+80
37
4
100
37+50
37+50+80
37
37+50
5
125
37+50+80
250V
37+50+80+100
37
0.03A
37+50
6
150
37+50+80
37+50+80+100
Above flow ranges are considered with water as medium
(at density = 1000 kg/m³, pressure = 1 atm, temperature = 25 ⁰ C)
'ON' falling flow
'ON' rising flow
(LPM)
(LPM)
Mini-
Maxi-
Mini-
Maxi-
mum
mum
mum
mum
15
50
25
60
45
100
50
110
50
140
60
160
100
240
110
260
50
160
60
180
225
480
230
520
140
320
150
340
320
750
380
860
210
550
225
635
105
320
115
340
500
1400
590
1700
350
1100
400
1300
200
580
230
680
730
1750
1030
2100
500
1500
650
2050
400
1000
475
1250
300
800
330
930
2650
3000
2750
3100
850
2400
990
2600
650
1800
750
1900
350
1450
450
1550
Maximum
operating
flow (LPM)
150
150
350
450
450
1000
1000
1300
1000
1000
2500
2000
2000
3000
3000
2000
2000
3200
3200
3200
3200
8