4.3
Models available
Designation
RS 200/M BLU
4.4
Technical data
Model
Type
Output
(1)
Fuel
Gas pressure at max. output
- Gas: G20 / G25 / G31
Operation
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2) Pressure at the test point of the pressure switch (Fig. 29 on page 29) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
The sound power is measured using the "Free Field" method, required by the EN 15036 standard, and according to an "Accuracy: Category 3"
measurement, as described in EN ISO 3746.
4.5
Electrical data
Model
Type
Main electrical supply
Auxiliary circuit electrical supply
Fan motor IE3
Ignition transformer
Absorbed electric power
Protection level
Technical description of the burner
Power supply voltage
TL
3 ~ 230 / 400V - 50Hz
Max.
kW
Mcal/h
Min.
kW
Mcal/h
mbar
(2)
–
–
°C
°C max
dB(A)
Hz
rpm
V
kW
A
V1 - V2
I1 - I2
kW max
Natural gas: G20 (methane) G21 - G22 - G23 - G25 - G31
Intermittent (min. 1 stop in 24 hours)
Progressive two-stage or modulating by kit (see ACCESSORIES).
Boilers: water, steam, diathermic oil
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
9
GB
Start-up
Direct
RS 200/M BLU
1106T
1380 ÷ 2400
1187 ÷ 2064
550
473
28 / 35.6 / 19.6
0 - 40
60
80.5
91.5
RS 200/M BLU
1106T
50
2935
400
5.5
10.2
230 V - 1 x 8 kV
1 A - 20 mA
5.9
IP 44
Code
20145799
Tab. B
Tab. C
Tab. D
20152093