7.3
DISPLAY AND TARGET INFORMATION
(1)
Settings Display
information:
Information / Settings
Software version
*Initiate OSC storage
Initiate fault data storage
CT ratio
PT ratio
Rated Freq.
CT secondary rating
Enable/disable readouts in primary I & V values
Positive line Reactance (:/unit distance)
multiplier for fault locator
Fault location, displayed
in Km. or miles DTYP KM or MI (miles)
Reclosing mode:TTYP
1)3PT on all faults, no RI.
2)3PT on all faults,
with 3RI on DG fault.
3)3PT on all faults,
with 3RI on DG/2D fault.
4)3PT on all faults w/3RI.
5)SPT on DG fault w/SRI,
3PT on MD fault w/o RI.
6)SPT on DG fault w/SRI,
3PT on MD fault w/3RI.
@*Single phasing limit timer
*Timer for pole-disagreement
RI on Z1 trip
RI on Z2 trip
RI on Z3 trip
RB on BF squelch
Remote pilot control
Pilot system selection:
1) 3-zone non pilot schemes
2) Zone-1 extension scheme
3) POTT or Unblocking scheme
4) PUTT scheme
5) Blocking scheme
FDOG trip delay timer
Blocking system channel coordination timer
Pilot phase unit
Pilot ground unit
Zone-1 phase unit
Zone-1 ground unit
Zone-1 delay trip
* Optional
@ 62T will not be available if JMP2 is not on 2-3 position
The setting display shows the following
Display
Function
Field
VERS
2.60
OSC
TRIP/Z2TR/Z2Z3/DVDI
FDAT
TRIP/Z2TR/Z2Z3
CTR
30-5000, (5)
VTR
100-7000, (5)
FREQ
60, 50
CTYP
5 or 1
RP
YES/NO
XPUD
0.300-1.5, in 0.001/DTYP
OFF
1PR
2PR
3PR
SPR
SR3R
62T
0.300-5.000 in 0.05 sec. steps
SPTT
1.000-6.000 in 1.0 sec. steps
Z1RI
YES/NO
Z2RI
YES/NO
Z3RI
YES/NO
BFRB
YES/NO
PLT
YES/NO
STYP
3ZNP
Z1E
POTT
PUTT
BLK
FDGT
0-15, in 1 cycle steps
BLKT
0-98, in 2 ms steps
PLTP
#0.01-50.00, 0.01 ohm steps
PLTG
#0.01-50.00, 0.01 ohm steps
Z1P
#0.01-50.00, 0.01 ohm steps
Z1G
#0.01-50.00, 0.01 ohm steps
T1
0-15, in 1 cycle steps
I.L. 40-385.5
Value
Field
7-3