Download Print this page

ABB XFC6200EX Startup Manual page 17

Advertisement

If a radio is used, verify directional antenna with correct frequency range
is pointed toward base (± 6°). The antenna should be mounted vertically,
with the vanes perpendicular to the ground. Verify that the radio is good,
with the same frequencies used for base radio and remote.
If a modem is used, verify dial tone on line at the telephone
company's termination box by checking Tip and Ring. Check wiring
from phone company's box to dial-up modem. If cellular, also check
for proper Tip & Ring voltage available. Insure phone number is
correct in the 6200EX and WinCCU.
Note: The telephone company uses a 48 volt power supply so the
typical on-hook voltage between the Tip and Ring wires
should be something less than 48 volts. Measuring another
way, Tip to ground is approx. zero volts and Ring to ground
is approx. –48 volts.
In the off-hook condition, Tip to ground will be approx. –20
volts while Ring to ground will be approx. –28 volts or
approx. 8 volts between Tip and Ring.
Wiring Documentation
Specific wiring drawings are sent with each 6200EX based on the
options ordered. Many wiring diagrams, including communications are
available on the web at http://www.abb.com/totalflow. To see if a diagram
is available, go to the web site, Select "Continuing Customer Service and
Support", and then select "Wiring Instructions". Communications pin-outs
of the 6200EX are shown on page 12 of this guide.