Dc inverter multi type; dc multi outdoor units (64 pages)
Summary of Contents for Kaysun Amazon V
Page 1
ENGINEERING DATA BOOK Amazon V K2F-252 DN5S K2F-500 DN5S K2F-730 DN5S K2F-280 DN5S K2F-560 DN5S K2F-785 DN5S K2F-335 DN5S K2F-615 DN5S K2F-850 DN5S K2F-400 DN5S K2F-670 DN5S K2F-900 DN5S K2F-450 DN5S Thank you very much for purchasing our air conditioner.
Page 2
Amazon V CONTENTS Part 1 General Information ............... 3 Part 2 Outdoor Unit Engineering Data ..........15 Part 3 System Design and Installation ........... 144...
Amazon V Part 1 General Information Indoor and Outdoor Unit Capacities ........4 External Appearance ..............6 Outdoor Unit Combinations ............8 Combination Ratio..............9 Selection Procedure ............. 10...
Amazon V 1 Indoor and Outdoor Unit Capacities 1.1 Indoor Units 1.1.1 Standard indoor units Table 1-1.1: Standard indoor unit abbreviation codes Abbreviation Abbreviation Type Type code code KCOF One-way Cassette KAYF Wall-mounted KCIF Compact Four-way Cassette KPCF Ceiling & Floor...
Page 6
Amazon V 1.2 Outdoor Units Table 1-1.5: Outdoor unit capacity range Capacity Model Name Combination Type K2F-252 DN5S 10HP K2F-280 DN5S 12HP K2F-335 DN5S 14HP K2F-400 DN5S 16HP K2F-450 DN5S 18HP K2F-500 DN5S 20HP K2F-560 DN5S 22HP K2F-615 DN5S 24HP...
Amazon V 2 External Appearance 2.1 Indoor Units 2.1.1 Standard indoor units Table 1-2.1: Standard indoor unit appearance One-way Cassette Compact Four-way Cassette KCOF KCIF Four-way Cassette Medium Static Pressure Duct KCIBF KPDF High Static Pressure Duct Wall-mounted KPDHF KAYF Ceiling &...
Page 8
Amazon V 2.2 Outdoor Units 2.2.1 Single units Table 1-2.4: Single outdoor unit appearance 8/10/12HP 14/16HP 18/20/22HP 24/26/28/30/32HP (with single fan) (with single fan) (with dual fans) (with dual fans) 2.2.2 Combinations of units Table 1-2.5: Combination outdoor unit appearance...
Table 1-5.1: Indoor and outdoor unit combination ratio limitations Maximum combination ratio Type Minimum combination ratio Standard indoor units only Amazon V outdoor units 150% Table 1-5.2: Combinations of Indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of connected indoor...
Amazon V 5 Selection Procedure 5.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Step 2: Select indoor units...
Page 12
Amazon V 5.2 Example The following is a selection example based on total heat load for cooling. Figure 1-6.1:Room plan Room H Room G Room A Room F Room B Room E Room C Room D Step 1: Establish design conditions ▪...
Page 13
Amazon V Table 1-6.2: Extract from medium static pressure duct (KPDF) cooling capacity table Indoor air temperature 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB Capacity Model index 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB...
Page 14
Amazon V Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of Maximum number of connected indoor units (standard Capacity connected indoor units index indoor units only) 50.0 250 to 750 56.0...
Page 15
Amazon V Find the correction factor for piping length and level difference (“K1”) Figure 1-6.3: V6rate of change in cooling capacity K1 = 0.898 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200...
Page 16
Amazon V Part 2 Outdoor Unit Engineering Data Specifications ................16 Dimensions ................19 Installation Space Requirements ..........23 Piping Diagrams ..............24 Wiring Diagrams ..............30 Electrical Characteristics ............32 Functional Components and Safety Devices ......33 Capacity Tables ..............34 Operating Limits ..............140 10 Sound Levels ............... 141...
Amazon V 2 Dimensions 2.1 Single Units 8/10/12HP Figure 2-2.1: 8/10/12 dimensions (unit: mm) Checkport (usedtomeasure system pressureandcharge additionalrefrigerant in maintenance process) Liquid pipe connection port (ΦA) Gas pipe connection port (ΦB) Detail R Table 2-2.1: 8/10/12HP connection piping diameter (unit: mm)
Page 21
Amazon V 14/16/18HP Figure 2-2.2: 14/16/18HPdimensions(unit: mm) Checkport(usedtomeasure system pressureandcharge additionalrefrigerant in maintenance process) Liquid pipe connection port (ΦA) Gas pipe connection port (ΦB) 1340 Detail R Table 2-2.1: 14/16HP connection piping diameter (unit: mm) Size 14HP 16HP 18HP Φ15.9 Φ15.9...
Page 22
Amazon V 20/22HP Figure 2-2.3: 20/22HP dimensions(unit: mm) Checkport(usedtomeasure system pressureandcharge additionalrefrigerant in maintenance process) Liquid pipe connection port (ΦA) Gas pipe connection port (ΦB) 1340 Detail R Table 2-2.1: 18/20/22HP connection piping diameter (unit: mm) Size 20HP 22HP Φ19.1 Φ19.1...
Page 23
Amazon V 24/26/28/30/32HP Figure 2-2.4: 24/26/28/30/32HP dimensions(unit: mm) Check port (usedto measuresystem pressure and charge additionalrefrigerant in maintenance process) Liquid pipe connection port (ΦA) Gas pipe connection port (ΦB) 1730 Detail R Table 2-2.1: 24/26/28/30/32HP connection piping diameter (unit: mm)
Amazon V 3 Installation Space Requirements For single unit installation For single row installation Figure 2-3.1: Single unit installation (unit: mm) Figure 2-3.2: Single row installation (unit: mm) >1000 >1000 100-500 >1000 >1000 >1000 >1000 Front 100-500 Front >1000 >1000 For multi-row installation Figure 2-3.3: Multi-row installation (unit: mm)
Amazon V 4 Piping Diagrams 8/10/12HP Figure 2-4.1: 8/10/12HP piping diagram E S C EXVA EXVC T7C1 Legend Parts name Parts name Compressor Plate heat exchanger Discharge temperature switch Accumulator High pressure switch Heat exchanger cooling electric control box High pressure sensor...
Page 26
Amazon V 14/16/18HP Figure 2-4.2: 14/16/18HP piping diagram EXVA EXVB EXVC T7C1 Legend Parts name Parts name Compressor Accumulator Discharge temperature switch Heat exchanger cooling electric control box High pressure switch Heat exchanger temperature sensor High pressure sensor Outdoor ambient temperature sensor...
Page 27
Amazon V 20/22/24HP Figure 2-4.3: 20/22/24HP piping diagram E S C EXVA EXVB EXVC T7C1 T7C2 Legend Parts name Parts name Compressor Accumulator Discharge temperature switch Heat exchanger cooling electric control box High pressure switch Heat exchanger temperature sensor High pressure sensor...
Page 28
Amazon V 26/28HP Figure 2-4.4: 26/28HP piping diagram EXVA EXVB EXVC T7C1 T7C2 Legend Parts name Parts name Compressor Accumulator Discharge temperature switch Heat exchanger cooling electric control box High pressure switch Heat exchanger temperature sensor High pressure sensor Outdoor ambient temperature sensor...
Page 29
Amazon V 30/32HP Figure 2-4.5: 30/32HP piping diagram EXVA EXVB EXVC T7C2 T7C1 Legend Parts name Parts name Compressor Heat exchanger cooling electric control box Discharge temperature switch Heat exchanger temperature sensor High pressure switch Outdoor ambient temperature sensor High pressure sensor...
Page 30
Amazon V Key components: 1. Oil separator: Separates oil from gas refrigerant pumped out ofthe compressor and quickly returns it to the compressor.Separation efficiency is up to 99%. 2. Accumulator: Stores liquid refrigerant and oil to protect compressor from liquid hammering.
Amazon V 7 Functional Components and Safety Devices Table 2-7.1: 8/10/12/14/16HP functional components and safety devices Item 10HP 12HP 14HP 16HP Discharge temperature switch Off: 115(±5) °C/ On: 75(±15) °C Compressor top and discharge pipe Compressor 90°C =5kΩ± 3% temperature sensors Crankcase heater 30W×2...
Page 100
Amazon V 8.2 Heating Capacity Tables Table 2-8.14: 8HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 21.06 6.05 20.98 6.15 20.54 6.40 20.47 6.58 20.45 6.76 20.34...
Page 101
Amazon V Table 2-8.14: 8HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 21.13 8.48 21.05 8.56 20.96 8.61 20.96 8.70 20.96 8.76 20.88 8.87 -19.8 22.11...
Page 102
Amazon V Table 2-8.14: 8HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 21.60 9.09 20.31 8.40 18.94 8.26 18.17 8.11 17.49 8.01 16.03 7.71 -19.8 21.60...
Page 103
Amazon V Table 2-8.15: 10HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 24.57 7.49 24.47 7.62 23.96 7.92 23.88 8.15 23.86 8.37 23.72 8.50 -19.8 25.83 7.69...
Page 104
Amazon V Table 2-8.15: 10HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 24.66 10.50 24.56 10.60 24.46 10.66 24.46 10.78 24.46 10.84 24.36 10.98 -19.8 25.80...
Page 105
Amazon V Table 2-8.15: 10HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 25.20 11.25 23.70 10.41 22.10 10.23 21.20 10.04 20.40 9.92 18.70 9.54 -19.8 25.20...
Page 106
Amazon V Table 2-8.16: 12HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 29.25 9.94 29.13 10.11 28.53 10.51 28.43 10.81 28.41 11.11 28.24 11.28 -19.8 30.75 10.20...
Page 107
Amazon V Table 2-8.16: 12HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 29.35 13.93 29.23 14.06 29.11 14.15 29.11 14.30 29.11 14.39 28.99 14.57 -19.8 30.71...
Page 108
Amazon V Table 2-8.16: 12HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 30.00 14.93 28.21 13.81 26.31 13.57 25.24 13.32 24.29 13.16 22.26 12.67 -19.8 30.00...
Page 109
Amazon V Table 2-8.17: 14HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 35.10 11.56 34.96 11.76 34.23 12.22 34.12 12.57 34.09 12.92 33.89 13.12 -19.8 36.90 11.86...
Page 110
Amazon V Table 2-8.17: 14HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 35.22 16.19 35.08 16.35 34.94 16.45 34.94 16.63 34.94 16.73 34.79 16.94 -19.8 36.86...
Page 111
Amazon V Table 2-8.17: 14HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 36.00 17.36 33.86 16.05 31.57 15.78 30.29 15.49 29.14 15.30 26.71 14.73 -19.8 36.00...
Page 112
Amazon V Table 2-8.18: 16HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 39.00 14.06 38.85 14.30 38.04 14.87 37.91 15.29 37.88 15.71 37.66 15.96 -19.8 41.00 14.43...
Page 113
Amazon V Table 2-8.18: 16HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 39.13 19.70 38.98 19.89 38.82 20.01 38.82 20.23 38.82 20.35 38.66 20.62 -19.8 40.95...
Page 114
Amazon V Table 2-8.18: 16HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 40.00 21.12 37.62 19.53 35.08 19.20 33.65 18.85 32.38 18.62 29.68 17.92 -19.8 40.00...
Page 115
Amazon V Table 2-8.19: 18HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 43.68 15.29 43.51 15.55 42.60 16.17 42.46 16.63 42.42 17.08 42.18 17.35 -19.8 45.92 15.69...
Page 116
Amazon V Table 2-8.19: 18HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 43.83 21.42 43.65 21.63 43.48 21.76 43.48 21.99 43.48 22.13 43.30 22.41 -19.8 45.87...
Page 117
Amazon V Table 2-8.19: 18HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 44.80 22.96 42.13 21.24 39.29 20.87 37.69 20.49 36.27 20.24 33.24 19.48 -19.8 44.80...
Page 118
Amazon V Table 2-8.20: 20HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 49.14 16.30 48.94 16.58 47.93 17.24 47.77 17.72 47.73 18.21 47.45 18.50 -19.8 51.66 16.72...
Page 119
Amazon V Table 2-8.20: 20HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 49.31 22.83 49.11 23.06 48.91 23.19 48.91 23.45 48.91 23.59 48.71 23.89 -19.8 51.60...
Page 120
Amazon V Table 2-8.20: 20HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 50.40 24.48 47.40 22.64 44.20 22.25 42.40 21.84 40.80 21.57 37.40 20.76 -19.8 50.40...
Page 121
Amazon V Table 2-8.21: 22HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 51.64 19.69 51.43 20.03 50.36 20.83 50.19 21.42 50.15 22.00 49.86 22.35 -19.8 54.28 20.21...
Page 122
Amazon V Table 2-8.21: 22HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 51.81 27.59 51.60 27.86 51.39 28.02 51.39 28.33 51.39 28.50 51.18 28.87 -19.8 54.22...
Page 123
Amazon V Table 2-8.21: 22HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 52.96 29.57 49.80 27.35 46.44 26.88 44.55 26.39 42.87 26.07 39.30 25.09 -19.8 52.96...
Page 124
Amazon V Table 2-8.22: 24HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 58.50 21.43 58.27 21.80 57.06 22.66 56.87 23.31 56.82 23.95 56.49 24.32 -19.8 61.50 21.99...
Page 125
Amazon V Table 2-8.22: 24HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 58.70 30.02 58.46 30.32 58.23 30.49 58.23 30.83 58.23 31.01 57.99 31.41 -19.8 61.43...
Page 126
Amazon V Table 2-8.22: 24HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 60.00 32.18 56.43 29.77 52.62 29.25 50.48 28.72 48.57 28.37 44.52 27.30 -19.8 60.00...
Page 127
Amazon V Table 2-8.23: 26HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 63.58 21.83 63.32 22.20 62.00 23.09 61.80 23.74 61.74 24.39 61.38 24.78 -19.8 66.83 22.40...
Page 128
Amazon V Table 2-8.23: 26HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 63.79 30.58 63.53 30.88 63.27 31.06 63.27 31.40 63.27 31.59 63.01 32.00 -19.8 66.75...
Page 129
Amazon V Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 65.20 32.78 61.32 30.32 57.18 29.80 54.85 29.26 52.78 28.90 48.38 27.81 -19.8 65.20 31.22 61.32 28.72 57.18 28.14 54.85...
Page 130
Amazon V Table 2-8.24: 28HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 65.65 24.95 65.38 25.38 64.02 26.39 63.81 27.13 63.76 27.88 63.38 28.32 -19.8 69.00 25.60...
Page 131
Amazon V Table 2-8.24: 28HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 65.87 34.95 65.60 35.29 65.33 35.50 65.33 35.89 65.33 36.10 65.07 36.57 -19.8 68.93...
Page 132
Amazon V Table 2-8.24: 28HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 67.32 37.47 63.32 34.65 59.04 34.06 56.64 33.44 54.50 33.02 49.96 31.78 -19.8 67.32...
Page 133
Amazon V Table 2-8.25: 30HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 74.11 23.55 73.81 23.96 72.27 24.91 72.03 25.62 71.97 26.32 71.55 26.74 -19.8 77.90 24.17...
Page 134
Amazon V Table 2-8.25: 30HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 74.36 33.00 74.05 33.32 73.75 33.52 73.75 33.89 73.75 34.09 73.45 34.53 -19.8 77.81...
Page 135
Amazon V Table 2-8.25: 30HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 76.00 35.37 71.48 32.72 66.65 32.16 63.94 31.57 61.52 31.18 56.40 30.01 -19.8 76.00...
Page 136
Amazon V Table 2-8.26: 32HP heating capacity Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 78.01 25.96 77.69 26.41 76.08 27.46 75.82 28.23 75.76 29.01 75.32 29.47 -19.8 82.00 26.64...
Page 137
Amazon V Table 2-8.26: 32HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 78.27 36.37 77.95 36.73 77.63 36.94 77.63 37.35 77.63 37.57 77.32 38.06 -19.8 81.90...
Page 138
Amazon V Table 2-8.26: 32HP heating capacity (continued) Indoor air temp. °C DB Outdoor 16.0 18.0 20.0 21.0 22.0 24.0 air temp. °C DB °C WB -25.4 80.00 38.98 75.24 36.06 70.16 35.44 67.30 34.79 64.76 34.36 59.37 33.07 -19.8 80.00...
Page 139
Amazon V 8.3 Capacity Correction Factors for Piping Length and Level Difference Figure 2-8.1: Rate of change in cooling capacity Figure 2-8.2: Rate of change in heating capacity 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200...
Page 140
Amazon V 8.4 Capacity Correction Factors for Frost Accumulation The heating capacity tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. If snow has accumulated against the outside surface of the outdoor unit heat exchanger heating capacity is reduced.
Amazon V Figure 2-10.6 26/28/30/32HP octave band level NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 1000 2000 4000 8000 Octave band center frequency (Hz) Accessories 11.1 Standard Accessories Table2-11.1: Standard accessories Name Shape Quantity Function Outdoor unit installation manual Outdoor unit owner’s manual...
Page 145
Amazon V Part 3 System Design and Installation Preface to Part 3 ..............145 Unit Placement and Installation .......... 146 Outdoor Unit Ducting and Shielding ........149 Refrigerant Piping Design ............ 155 Refrigerant Piping Installation ..........165 Drain Piping ............... 177 Insulation ................
The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Kaysun Amazon V Series VRF project. Additional important information which may primarily be of use during field installa- tion has been placed in boxes, such as the example below, titled “Notes for installers”.
Amazon V 2 Unit Placement and Installation 2.1 Outdoor Units 2.1.1 Placement considerations Placement of outdoor units should take account of the following considerations: ▪ Air conditioners should not be exposed to direct radiation from a high-temperature heat source. ▪ Air conditioners should not be installed in positions where dust or dirt may affect heat exchangers.
Page 148
Amazon V 2.1.3 Master and slave unitpositioning In systems withmultipleoutdoor units, the units should be placed in order from largest capacity unit to smallest capacity unit. The largest capacity unit must be placed on the first branch, and be set as the master unit, while the others should be set as slave units.
Page 149
Amazon V Figure 3-2.5: Outdoor unit typicalconcrete base structure design (unit: mm) Outdoor unit Φ10 Expansion bolt Rubber anti-vibrat i on pads Rubber anti-vibration pads Solid ground / surface Concrete base h=200 ≥80 Figure 3-2.6: Expansion bolt positioning Table 3-2.1: Expansion bolt spacings...
Amazon V 2.2 Indoor Units 2.2.1 Placementconsiderations Placement of indoor units should take account of the following considerations: ▪ Sufficient space for drain piping and for access during servicing and maintenance should be allowed. ▪ To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) should be avoided.
Page 151
Amazon V 3.3 Ducting for 8HP, 10HP and 12HP Units 3.3.1 Option A – Transverse ducting Figure 3-3.2: Transverse ducting for 8HP, 10HP and 12HP units (unit: mm) Suppo Radius E 8×S T3.9 self‐thread ding screws Remove the steel mesh fi Air outlet louver Table 3-3.1: Duct dimensions Table 3-3.2: External static pressure...
Page 152
Amazon V Ducting for 14HP and 16HP Units 3.3.3 Option A – Transverse ducting Figure 3-3.4: Transverse ducting for 14HP and 16HP units (unit: mm)) × × ST3.9 Support Radius self‐thre eading screws Radius θ Remove e the steel mes sh first Air out let louver Table 3-3.5: Duct dimensions...
Page 153
Amazon V Ducting for 18HP, 20HP and 22HP Units 3.3.5 Option A – Transverse ducting Figure 3-3.6: Transverse ducting for 18HP, 20HP and 22HP units (unit: mm)) Support 1290 0 × ST3.9 Radiu eading screws Radius θ Remove t steel meshe es first Air ou u tlet louver Table 3-3.9: Duct dimensions...
Page 154
Amazon V Ducting for 24HP, 26HP, 28HP, 30HP and 32HP Units 3.3.7 Transverse ducting only Figure 3-3.8: Transverse ducting for 24HP, 26HP, 28HP, 30HP and 32HP units (unit: mm)) pport 2 × ST3.9 Radius self‐thre eading screws 1653 Radius Remove t θ steel meshe es first...
Page 155
Amazon V 3.4 Fan Performance The default external static pressure of outdoor units’ air outlets iszero. With the steel mesh cover removed the external static pressure is 20Pa. Figure 3-3.9: 8-12HP units fan performance Figure 3-3.10: 14-16HP units fan performance...
Amazon V 3.5 Snow Shielding In areas of high snowfall, snow shields should be installed on air inlets and outlets to prevent snow from entering the units. Additionally, the height of the base structures should be increased so as to raise the units further off the ground.
Page 157
Amazon V 4.3 Permitted Piping Lengths and Level Differences The piping length and level difference requirements that apply are summarized in Table 3-4.3 and are fully described as follows (refer to Figure 3-4.2): 1. Requirement 1: The total length of piping in one refrigerant system should not exceed 1000m. When calculating the...
Page 158
Amazon V Figure 3-4.2: Permitted refrigerant piping lengths and level differences (12) (32) (22) (140) 3(71) (140) 4(140) 7(28) 8(140) (140) (112) (71) (112) (140) (28) (140) (56) (140) (56) (140) Piping between farthest indoor unit and first indoor branch joint≤40m Equivalent length of piping between farthest indoor unit and first outdoor branch joint≤200m...
Page 159
Amazon V 4.4 Selecting Piping Diameters Tables 3-4.4 to 3-4.8, below, specify the required pipe diameters for the indoor and outdoor piping.The main pipe (L ) and first indoor branch joint (A) should be sized according to whichever of Tables 3-4.4 and 3-4.5 indicates the larger size.
Page 160
Amazon V Table 3-4.5: Main pipe ) and first indoor branch joint (A) Pipe size length of all liquid pipe equivalent <90 m Pipe size length of all liquid pipe equivalent ≥90 m Total capacity of Pipe size mm (inches)
Page 161
Amazon V 4.5 Refrigerant Piping Selection Example The example below illustrates the piping selection procedure for a system consisting of three outdoor units (32HP + 22HP + 12HP) and 17 indoor units. The system’s equivalent total piping length is in excess of 90m; the piping between the farthest indoor unit and the first indoor branch joint is less than 40m in length;...
Page 162
Amazon V 4.6 Branch Joints Branch joint design should take account of the following: ▪ U-shaped branch joints should be used – tee joints are not suitable. Branch joint dimensions are given in Tables 3-4.9 and 3-4.10. ▪ To avoid accumulation of oil in the outdoor units, outdoor branch joints should be installed horizontally and must not be higher than the outdoor unit refrigerant outlets.
Page 163
Amazon V Table 3-4.9: Indoor branch joint dimensions (unit: mm) Model Gas side joints Liquid side joints KCMI 112 KCMI 212 KCMI 312 KCMI 412 KCMI 512...
Page 164
Amazon V Table 3-4.10: Outdoor branch joint dimensions (unit: mm) Model Gas side joints Liquid side joints KCME12.6 KCME13.6...
Page 165
Amazon V 4.7 Refrigerant Leakage Precautions R410A refrigerantis not flammable in air at temperatures up to 100°C at atmospheric pressure and is generally considered a safe substance to use in air conditioning systems. Nevertheless, precautions should be taken to avoid danger to life in the unlikely event of a major refrigerant leakage.
Amazon V 5 Refrigerant Piping Installation 5.1 Procedure and Principles 5.1.1 Installation procedure Notes for installers Installation of therefrigerant piping system should proceed in the following order: Pipe Pipe brazing and Pipe flushing Gastightness test Joint insulation Vacuum drying...
Page 167
Amazon V 5.2 Storing Copper Piping 5.2.1 Pipe delivery, storage and sealing Notes for installers ▪ Ensure that piping does not get bent or deformed during delivery or whilst stored. ▪ On construction sites store piping in a designated location.
Page 168
Amazon V 5.3.3 Expanding copper piping ends Notes for installers ▪ Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed. ▪ Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head.
Page 169
Amazon V 5.3.5 Bending piping Bending copper piping reduces the number of brazed joints required and can improve quality and save material. Notes for installers Piping bending methods ▪ Hand bending is suitable for thin copper piping (Ф6. 35mm -Ф12. 7mm).
Page 170
Amazon V 5.5 Brazing Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even compressor failure.
Page 171
Amazon V … box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. Figure 3-5.6: Piping orientation during brazing Piping overlap during brazing Table 3-5.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints on piping of different diameters.
Page 172
Amazon V 5.6 Branch Joints Notes for installers ▪ Use U-shaped branch joints as specified on the Figure 3-5.8: Branch joint orientation construction drawings – do not replace U-shaped branch joints with tee joints. ▪ To avoid accumulation of oil in the outdoor units,...
Page 173
Amazon V 5.7 Piping Connections between Outdoor Units The piping connecting the outdoor units should be horizontal and must not be higher than the refrigerant outlets. If necessary, to avoid obstacles the piping may be vertically offset below the outlets. When inserting a vertical offset to avoid an obstacle, the whole outdoor piping should be offset, rather than just the section adjacent to the obstacle.
Page 174
Amazon V 5.8.2 Procedure Notes for installers Warning Only use nitrogen for flushing.Using carbon dioxide risks leaving condensation in the piping.Oxygen, air, refrigerant, flammable gases and toxic gases must not be used for flushing. Use of such gases may result in fire or explosion.
Page 175
Amazon V 5.9 Gastightness Test 5.9.1 Purpose To prevent faults caused by refrigerant leakage, a gastightness test should be performed beforesystem commissioning.. 5.9.2 Procedure Notes for installers Warning Only drynitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be used for gastightness testing.
Page 176
Amazon V 5.9.3 Leak detection Notes for installers The general methods for identifying the source of a leak are as follows: 1. Audio detection: relatively large leaks are audible. 2. Touch detection: place your hand at joints to feel for escaping gas.
Page 177
Amazon V 5.10.2 Procedure Notes for installers During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C.
Amazon V 6 Drain Piping 6.1 Design Considerations Drain piping design should take account of the following considerations: ▪ Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced at the indoor units and installed at a slope sufficient to allow drainage. Discharge as close as possible to the indoor units is usually preferable.
Page 179
Amazon V Figure 3-6.5: Drain piping air vents Vent ▪ Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should not come into direct contact with the ground. ▪ Drain piping diameter should be not less than the indoor units’ drain piping connection.
Page 180
Amazon V Table 3-6.2: Vertical drain piping diameters Nominal PVC piping Capacity (L/h) Remarks diameter(mm) PVC25 Branch piping only PVC32 PVC40 PVC50 1440 Branch or main piping PVC63 2760 PVC75 5710 PVC90 8280 6.4 Drain Pipingfor Units with Lift Pumps Drain piping for units with lift pumps should take account of the followingadditional considerations: ▪...
Amazon V 6.6 Watertightness Test and Water Flow Test Once installation of a drainage piping system is compete, watertightness and water flow tests should be performed. Notes for installers Watertightness test ▪ Fill the piping with water and test for leakages over a 24-hour period.
Page 182
Amazon V 7.1.4 Installation of piping insulation With the exception of joint insulation, insulation should be applied to piping before fixing the piping in place. Insulation at joints in refrigerant piping should be applied after the gastightness test has been completed.
Amazon V 8 Charging Refrigerant 8.1 Calculating Additional Refrigerant Charge The additional refrigerant charge required depends on the lengths and diameters of the outdoor and indoor liquid pipes. Table 3-8.1 shows the additional refrigerant charge required per meter of equivalent pipe length for different diameters of pipe.
Page 184
Amazon V … box continued from previous page Step 3 • Open the valve where the yellow hose meets the pressure gauge, and open the refrigerant tank slightly to let the refrigerant eliminate the air. Caution: open the tank slowly to avoid freezing your hand.
Amazon V 9 Electrical Wiring 9.1 General Notes for installers Caution ▪ All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionalsand in accordance with all applicable legislation. ▪ Electrical systems should be grounded in accordance with all applicable legislation.
Page 186
Amazon V Figure 3-9.1: Outdoor unit power supply wiring Figure 3-9.2: Indoor unit power supply wiring Notes for installers The 3-phase, 380-415V, 50 or 60Hz power supplyshould be connected to the outdoor unit power supply terminals as shown in Figure 3-9.3.
Page 187
Amazon V ▪ Indoor communication wiring: ▪ The P QE communication wires should be connected one unit after another in a daisy chain from the outdoor unit to the final indoor unit as shown in Figure 3-9.4. At the final indoor unit, a 120Ω resistor should be connected between the P and Q terminals.After the final indoor unit, the communication wiring should NOT be continued...
Page 188
Amazon V Notes for installers The communication wires should be connected to the master outdoor unit terminals indicated in Figure 3-9.5 and Table 3-9.1. Caution ▪ Communication wiring has polarity. Care should be taken to connect the poles correctly.
Amazon V Installation in Areas of High Salinity 10.1 Caution Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. Outdoor units installed in seaside locationsshould be placed such as to avoid direct exposure to the sea air and additional...
Amazon V Commissioning 11.1 Outdoor Unit Address and Capacity Settings Before running a system for the first time, set each outdoor unit’s address on switch ENC1 on each outdoor unit’s main PCB. Refer to Table 3-11.1. The capacity of each outdoor unit (on switch ENC2 on each outdoor unit’s main PCB) is factory- set and should not need changing.
Page 191
Once all the pre-commissioning checks in Part 3, 11.3“Pre-commissioning Checks” have been completed, a test run should be performed as described below and a Amazon V Series System Commissioning Report (see Part 3, 12“Appendix to Part 3 – System Commissioning Report”) should be completed as a record of the operating status of the system during commissioning.
Amazon V Appendix to Part 3 –System Commissioning Report A total of up to 11 report sheets should be completed for each system: ▪ One Sheet A, one Sheet B and one Sheet C per system. ▪ One Sheet D and one Sheet Eper outdoor unit.
Page 193
Amazon V Amazon V Series System Commissioning Report– Sheet A SYSTEM INFORMATION Project name and location Customer company System name Installation company Commissioning date Agent company Outdoor ambient temp. Commissioning engineer Power supply (V) OUTDOOR UNIT INFORMATION Master unit Slave unit 1...
Page 194
Amazon V Amazon V Series System Commissioning Report– Sheet B Project name and location System name OUTDOOR UNITS Master unit Slave unit 1 Slave unit 2 Slave unit 3 Compressor suction pipe temperature System pressure at check port Phase currents (A)
Page 195
Amazon V Amazon V Series System Commissioning Report– Sheet C Project name and location System name RECORD OF ISSUES SEEN DURING COMMISSIONING Serial no. of relevant Description of observed issue Suspected cause Troubleshooting undertaken unit OUTDOOR UNIT FINAL CHECKLIST Master unit...
Page 196
Amazon V Amazon V Series System Commissioning Report– Sheet D Project name and location System name Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode 0.-- Unit address Master unit: 0; slave units: 1, 2, 3 1.--...
Page 197
Amazon V Amazon V Series System Commissioning Report– Sheet E Project name and location System name … table continued from previous page Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode 35.-- Reserved 36.-- DC voltage A Actual value = value displayed ×...