ENGINEERING DATA BOOK Amazon Unitario FD KMF-252 DN6 KMF-400 DN6 KMF-560 DN6 KMF-280 DN6 KMF-450 DN6 KMF-615 DN6 KMF-335 DN6 Please read this manual carefully and keep it for future reference. All the pictures in this manual are for illustration purpose only.
Page 3
AMAZON UNITARIO FD CONTENTS Part 1 General Information .................3 Part 2 Outdoor Unit Engineering Data ............12 Part 3System Design and Installation ............105...
AMAZON UNITARIO FD Part 1 General Information 1 Outdoor Unit Capacities ................4 2 External Appearance .................5 3 Combination Ratio ..................6 4 Selection Procedure ..................7...
Page 6
Table 1-1.5: Outdoor unit capacity range Capacity Model Name Combination Type KMF-252 DN6 10HP KMF-280 DN6 12HP KMF-335 DN6 14HP KMF-400 DN6 16HP KMF-450 DN6 20HP KMF-560 DN6 22HP KMF-615 DN6 Notes: 1. Amazon unitario FD outdoor units could not be combined.
Page 8
AMAZON UNITARIO FD 3 Combination Ratio Sum of capacity indexes of the indoor units Combination ratio = Capacity index of the outdoor units Table 1-5.1: Indoor and outdoor unit combination ratio limitations Maximum combination ratio Minimum Type Fresh air processing...
AMAZON UNITARIO FD 4 Selection Procedure 4.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Step 2: Select indoor units...
Page 10
AMAZON UNITARIO FD 4.2 Example The following is a selection example based on total heat load for cooling. Figure 1-6.1: Room plan Room H Room G Room A Room F Room B Room E Room C Room D Step 1: Establish design conditions ■ Indoor air temperature 25.8°C DB, 18°C WB; outdoor air temperature 33°C DB.
Page 11
AMAZON UNITARIO FD Table 1-6.2: Extract from medium static pressure duct (T2) cooling capacity table Indoor air temperature Capacity Model 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB index 20°C DB 23°C DB 26°C DB 27°C DB...
Page 12
AMAZON UNITARIO FD Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units Outdoor unit capacity Sum of capacity indexes of Maximum number of connected indoor units (standard Capacity connected indoor units indoor units only) index 25.2 126 to 327.6 28.0...
Page 13
AMAZON UNITARIO FD c) Find the correction factor for piping length and level difference (“K1”) Figure 1-6.3: Amazon unitario FD rate of change in cooling capacity K1=0.927 Notes: 1. The horizontal axis shows equivalent length of piping between farthest indoor unit and first outdoor branch joint; the vertical axis shows the largest level difference between indoor unit and outdoor unit. For level differences, positive values indicate that the outdoor unit is above the indoor unit, negative values indicate that the outdoor unit is below the indoor unit. d) Calculate the corrected capacity of KMF-560 DN6 (“C”) by using K1: C = B ×...
AMAZON UNITARIO FD 3 Installation Space Requirements There are obstacles on the air inlet side but no obstacles on the air outlet side and above the outdoor unit Figure 2-3.1:One outdoor unit installation (unit: mm) Figure 2-3.2:More than one outdoor unit installation (unit: mm) There are obstacles on the air inlet side and above the outdoor unit but no obstacles on the air outlet side Figure 2-3.3:One outdoor unit installation (unit: mm)
Page 20
AMAZON UNITARIO FD There are obstacles on the air outlet side and above the outdoor unit but no obstacles on the air inlet side Figure 2-3.7:One outdoor unit installation (unit: mm) Figure 2-3.8:More than one outdoor unit installation (unit: mm) ≥300...
Page 21
AMAZON UNITARIO FD Table 2-3.1 Condition 0<L2<1/2H 1000 1500 L2≤H 1/2H≤L2≤H 1250 1750 L2>H Install air duct to exhaust the air out of the space. Figure 2-3.13:One outdoor unit installation (unit: mm) Figure 2-3.14:More than one outdoor unit installation (unit: mm) ≥300...
Page 22
AMAZON UNITARIO FD When outdoor units are installed in different rows on a rooftop Figure 2-3.17: One outdoor unit installation (unit: mm) Figure 2-3.18:More than one outdoor unit are installed in each row (unit: Notes: 1. H is the height of the outdoor unit.
AMAZON UNITARIO FD 4 Piping Diagrams 8-14HP Figure 2-4.1: 8-14HP piping diagram EEVA E S C T7C1 EEVC INV1 Heat SV8A Legend Parts name Parts name Inverter Compressor Charge port Oil separator Low pressure sensor High pressure switch Gas-liquid separator...
Page 24
AMAZON UNITARIO FD 16-22HP Figure 2-4.2: 16-22HP piping diagram EEVA E S C T7C1 EEVC INV1 Heat SV8A Legend Parts name Parts name Inverter Compressor Charge port Oil separator Low pressure sensor High pressure switch Gas-liquid separator Check value Muffler...
Page 25
AMAZON UNITARIO FD Key components: 1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Gas-liquid separator: Separates liquid refrigerant from gas refrigerant, stores liquid refrigerant and oil to protect compressor from liquid hammering.
Page 27
AMAZON UNITARIO FD Legend Code Name Code Name COMP Compressor Main exchanger pipe temperature sensor EEVA/EEVC Electronic expansion valve Outdoor ambient temperature sensor FAN A/ FAN B DC Fan Liquid pipe temperature sensor HEAT A Crankcase heater Microchannel heat exchanger inlet pipe temperature sensor...
AMAZON UNITARIO FD 8.2 Heating Capacity Tables Table2-8.9:8HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 17.30 7.72 17.22 8.00 17.15 8.29 17.12 8.44 17.09 8.60 17.04...
Page 66
AMAZON UNITARIO FD Table2-8.9:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 17.04 7.86 16.97 8.15 16.91 8.46 16.89 8.62 16.86 8.78 16.82 9.14 -25.0 -25.4 17.93...
Page 67
AMAZON UNITARIO FD Table2-8.9:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 16.89 8.29 16.84 8.60 16.79 8.94 16.71 9.15 16.70 9.85 16.70 11.32 -25.0 -25.4 17.77...
Page 68
AMAZON UNITARIO FD Table2-8.9:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 17.07 9.83 16.74 10.63 16.16 9.86 15.58 9.39 15.01 9.04 13.85 8.54 -25.0 -25.4 17.97...
Page 69
AMAZON UNITARIO FD Table2-8.9:8HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 13.19 7.97 12.37 7.64 11.54 7.28 11.13 7.06 10.72 6.83 9.89 6.36 -25.0 -25.4 13.89...
Page 70
AMAZON UNITARIO FD Table2-8.10:10HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 19.23 8.20 19.17 8.51 19.12 8.84 19.10 9.02 19.08 9.20 19.05 9.57 -25.0 -25.4 20.25...
Page 71
AMAZON UNITARIO FD Table2-8.10:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 18.94 8.51 18.90 8.84 18.86 9.20 18.85 9.38 18.84 9.57 18.83 9.98 -25.0 -25.4 19.94...
Page 72
AMAZON UNITARIO FD Table2-8.10:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 18.70 9.03 18.68 9.40 18.64 9.94 18.61 10.56 18.59 11.36 18.55 12.36 -25.0 -25.4 19.68...
Page 73
AMAZON UNITARIO FD Table2-8.10:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 18.36 12.00 18.33 12.60 18.09 12.00 18.18 11.50 17.51 10.98 16.16 10.01 -25.0 -25.4 19.32...
Page 74
AMAZON UNITARIO FD Table2-8.10:10HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 15.39 9.33 14.43 8.86 13.47 8.41 12.99 8.15 12.50 7.89 11.54 7.34 -25.0 -25.4 16.20...
Page 75
AMAZON UNITARIO FD Table2-8.11:12HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 19.53 7.57 19.42 7.86 19.33 8.16 19.28 8.32 19.24 8.48 19.16 8.82 -25.0 -25.4 20.55...
Page 76
AMAZON UNITARIO FD Table2-8.11:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 19.29 7.79 19.19 8.09 19.11 8.41 19.07 8.58 19.03 8.75 18.96 9.10 -25.0 -25.4 20.30...
Page 77
AMAZON UNITARIO FD Table2-8.11:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 18.78 2.20 18.69 2.29 18.61 2.40 18.58 2.45 18.55 2.50 18.49 2.62 -25.0 -25.4 19.77...
Page 78
AMAZON UNITARIO FD Table2-8.11:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 17.98 9.88 17.89 11.02 17.81 12.00 17.78 12.37 17.75 12.33 18.46 11.55 -25.0 -25.4 18.92...
Page 79
AMAZON UNITARIO FD Table2-8.11:12HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 18.32 10.96 17.18 10.14 16.03 9.35 15.46 8.96 14.89 8.61 13.74 7.96 -25.0 -25.4 19.29...
Page 80
AMAZON UNITARIO FD Table2-8.12:14HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 20.61 8.58 20.49 8.91 20.39 9.24 20.33 9.42 20.28 9.60 20.19 9.98 -25.0 -25.4 21.69...
Page 81
AMAZON UNITARIO FD Table2-8.12:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 19.89 8.66 19.97 9.00 19.87 9.35 20.03 9.73 19.78 9.72 19.90 10.31 -25.0 -25.4 20.94...
Page 82
AMAZON UNITARIO FD Table2-8.12:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 19.50 9.17 19.40 9.52 19.31 9.89 19.26 10.08 19.09 10.28 19.02 10.70 -25.0 -25.4 20.52...
Page 83
AMAZON UNITARIO FD Table2-8.12:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 18.66 9.91 18.56 10.54 18.48 11.76 18.44 12.47 18.27 13.14 18.20 14.22 -25.0 -25.4 19.64...
Page 84
AMAZON UNITARIO FD Table2-8.12:14HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 17.86 14.09 17.77 13.87 17.68 13.02 17.64 12.45 17.48 11.90 16.49 10.81 -25.0 -25.4 18.80...
Page 85
AMAZON UNITARIO FD Table2-8.13:16HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 24.41 9.04 24.27 9.40 24.15 9.77 24.09 9.97 24.03 10.17 23.92 10.59 -25.0 -25.4 25.69...
Page 86
AMAZON UNITARIO FD Table2-8.13:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 23.94 9.29 23.81 9.67 23.69 10.06 23.64 10.26 23.58 10.47 23.48 10.91 -25.0 -25.4 25.20...
Page 87
AMAZON UNITARIO FD Table2-8.13:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 23.29 9.67 23.17 10.06 23.06 10.49 23.01 10.71 22.97 10.93 22.88 11.42 -25.0 -25.4 24.51...
Page 88
AMAZON UNITARIO FD Table2-8.13:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 22.29 10.49 22.17 10.94 22.07 12.06 22.02 12.96 21.98 13.91 21.90 15.29 -25.0 -25.4 23.46...
Page 89
AMAZON UNITARIO FD Table2-8.13:16HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 21.33 15.35 21.22 14.20 21.12 12.98 20.61 12.37 19.85 11.78 18.32 10.67 -25.0 -25.4 22.45...
Page 90
AMAZON UNITARIO FD Table2-8.15:20HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 29.98 11.14 29.81 11.60 29.64 12.08 29.55 12.33 29.47 12.59 29.33 13.13 -25.0 -25.4 31.56...
Page 91
AMAZON UNITARIO FD Table2-8.15:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 29.34 11.38 29.18 11.85 29.02 12.35 28.95 12.61 28.87 12.88 28.74 13.45 -25.0 -25.4 30.89...
Page 92
AMAZON UNITARIO FD Table2-8.15:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 28.48 12.40 28.33 12.92 28.18 13.47 28.11 13.75 28.04 14.05 27.92 14.67 -25.0 -25.4 29.98...
Page 93
AMAZON UNITARIO FD Table2-8.15:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 27.26 13.44 27.11 14.02 26.97 14.63 26.90 14.96 26.84 15.30 26.72 19.72 -25.0 -25.4 28.69...
Page 94
AMAZON UNITARIO FD Table2-8.15:20HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 26.09 13.55 25.94 13.71 26.93 15.79 25.97 15.10 25.01 14.00 23.09 13.10 -25.0 -25.4 27.46...
Page 95
AMAZON UNITARIO FD Table2-8.16:22HP heating capacity Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 31.21 11.84 31.03 12.32 30.85 12.83 30.77 13.09 30.68 13.36 30.52 13.92 -25.0 -25.4 32.86...
Page 96
AMAZON UNITARIO FD Table2-8.16:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 30.60 12.21 30.42 12.71 30.25 13.23 30.17 13.50 30.10 13.78 29.95 14.36 -25.0 -25.4 32.21...
Page 97
AMAZON UNITARIO FD Table2-8.16:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 29.72 12.79 29.55 13.32 29.39 13.89 29.31 14.18 29.24 14.48 29.11 15.12 -25.0 -25.4 31.28...
Page 98
AMAZON UNITARIO FD Table2-8.16:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor air temp. 16.0 18.0 20.0 21.0 22.0 24.0 °C DB °C WB -29.8 -30.0 28.44 13.77 28.28 14.35 28.12 14.98 28.05 15.30 27.98 15.65 27.86 16.36 -25.0 -25.4 29.94...
Page 99
AMAZON UNITARIO FD Table2-8.16:22HP heating capacity(continued) Indoor air temp. °C DB Outdoor air 16.0 18.0 20.0 21.0 22.0 24.0 temp. °C DB °C WB -29.8 -30.0 27.22 16.32 27.06 19.66 29.50 18.95 28.44 17.92 27.39 17.08 25.28 15.34 -25.0 -25.4 28.65...
Page 100
AMAZON UNITARIO FD 8.3 Capacity Correction Factors for Piping Length and Level Difference Figure 2-8.1: Rate of change in cooling capacity Figure 2-8.2: Rate of change in heating capacity Note: 1. The horizontal axis shows equivalent length of piping between farthest indoor unit and outdoor unit; the vertical axis shows the largest level difference between indoor unit and outdoor unit.
Page 101
AMAZON UNITARIO FD 8.4 Capacity Correction Factors for Frost Accumulation The heating capacity tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. If snow has accumulated against the outside surface of the outdoor unit heat exchanger heating capacity is reduced.
AMAZON UNITARIO FD 10 Sound Levels 10.1 Overall Table 2-10.1: Sound pressure level Model dB(A) 10HP 12HP 14HP 16HP 20HP 22HP Note: 1. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.
AMAZON UNITARIO FD 11 Accessories 11.1 Standard Accessories Table 2-11.1: Standard accessories Name Shape Quantity Function owner's and installation manual S-shaped connection pipe To connect gas and liquid pipes Build-out resistor To improve communication stability Elbow To connect gas pipes...
Page 107
AMAZON UNITARIO FD Part 3 System Design and Installation 1 Preface to Part 3 ................... 106 2 Unit Placement and Installation ............107 3 Outdoor Unit Ducting and Shielding ............113 4 Refrigerant Piping Design ..............115 5 Refrigerant Piping Installation ............... 124 6 Drain Piping ..................
The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Kaysun Amazon unitario FD Series VRF project. Additional important information which may primarily be of use during field installation has been placed in boxes, such as the example below, titled “Notes for installers”.
AMAZON UNITARIO FD 2 Unit Placement and Installation 2.1 Outdoor Units 2.1.1 Placement considerations Placement of outdoor units should take account of the following considerations: ■ Air conditioners should not be exposed to direct radiation from a high-temperature heat source.
Page 110
AMAZON UNITARIO FD 2.1.3 Base structures Outdoor unit base structure design should take account of the following considerations: ■ The base of the outdoor unit must use the solid concrete surface as the cement base or the steel beam frame base.
Page 111
AMAZON UNITARIO FD 2.1.5 Hoisting Notes for installers ■ Do not remove any packaging before hoisting. If units are not packaged or if the packaging is damaged, use suitable boards or packing material to protect the units. ■ Hoist one unit at a time, using two ropes to ensure stability.
AMAZON UNITARIO FD 2.2 Indoor Units 2.2.1 Placement considerations Placement of indoor units should take account of the following considerations: ■ Sufficient space for drain piping and for access during servicing and maintenance should be allowed. ■ To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) should be avoided.
Page 113
AMAZON UNITARIO FD 3 Outdoor Unit Ducting and Shielding 3.1 Ducting Requirements Figures 2-3.1 to Figures 2-3.20 show spacing requirements in different scenarios. If the installation space requirement cannot be met due to special installation conditions, the air duct should be installed.
AMAZON UNITARIO FD 3.5 Installation direction It is forbidden to install the outdoor unit horizontally along the base to avoid snow and ice accumulation that may hinder the drainage of the chassis. Figure 3-3.9: Installation direction with snow shield Snow drift...
AMAZON UNITARIO FD 4 Refrigerant Piping Design 4.1 Design Considerations Refrigerant piping design should take account of the following considerations: ■ The amount of brazing required should be kept to a minimum. ■ On the two inside sides of the first indoor branch joint (“A” in Figures 3-4.1 and 3-4.4) the system should, as far as possible, be equal in terms of number of units, total capacities and total piping lengths.
Page 118
AMAZON UNITARIO FD 4.3 Permitted Piping Lengths and Level Differences The piping length and level difference requirements that apply are summarized in Table 3-4.2 and are fully described as follows (refer to Figure 3-4.1): Figure 3-4.1: Permitted refrigerant piping lengths and level differences Branch joint Equivalent length of piping between farthest indoor unit and outdoor unit≤175m...
Page 119
AMAZON UNITARIO FD 1. Requirement 1: The piping between the farthest indoor unit (N14) and outdoor unit should not exceed 150m (actual length) and 175m (equivalent length). (The equivalent length of each branch joint is 0.5m, and the equivalent length of each branch header is 1m.)
Page 120
AMAZON UNITARIO FD 4.4 Selecting Piping Diameters Tables 3-4.6 to 3-4.8, below, specify the required pipe diameters for the indoor and outdoor piping. Figure 3-4.3: Selecting piping diameters Branch joint Equivalent length of piping between farthest indoor unit and outdoor unit≤175m Indoor unit Piping between farthest indoor unit and first indoor branch joint ≤...
Page 121
AMAZON UNITARIO FD 4.4.2 Diameters of Indoor main pipes and indoor branch joint kits Based on the total capacity of the indoor unit, select the branch joint for the indoor unit from the following table Table 3-4.7: Indoor main pipes (L2 to L11) and indoor branch joint kits...
Page 122
AMAZON UNITARIO FD 4.5 Refrigerant Piping Selection Example The example below illustrates the piping selection procedure for a system consisting of one outdoor unit (22HP) and 12 indoor units. The system's equivalent length between the farthest indoor unit and the outdoor unit is in excess of 90m;...
Page 123
AMAZON UNITARIO FD ■ The indoor units (N12 to N13) downstream of indoor branch joint H have total capacity of 2.8*2=5.6kW. Refer to Table 3-4.7. Indoor main pipe L8 is Φ15.9 / Φ 9.52. Indoor branch joint H is FQZHN-01D.
Page 124
AMAZON UNITARIO FD Table 3-4.9: Indoor branch joint dimensions (unit: mm) (continued) Model Gas side joints Liquid side joints FQZHN-02D FQZHN-03D FQZHN-04D FQZHN-05D FQZHN-06D FQZHN-07D...
Page 125
AMAZON UNITARIO FD 4.7 Refrigerant Leakage Precautions R410A refrigerant is not flammable in air at temperatures up to 100°C at atmospheric pressure and is generally considered a safe substance to use in air conditioning systems. Nevertheless, precautions should be taken to avoid danger to life in the unlikely event of a major refrigerant leakage.
AMAZON UNITARIO FD 5 Refrigerant Piping Installation 5.1 Procedure and Principles 5.1.1 Installation procedure Notes for installers Installation of the refrigerant piping system should proceed in the following order: Pipe Pipe brazing Gastightness Joint Pipe Vacuum drying insulation and installation...
Page 127
AMAZON UNITARIO FD 5.2 Storing Copper Piping 5.2.1 Pipe delivery, storage and sealing Notes for installers ■ Ensure that piping does not get bent or deformed during delivery or whilst stored. ■ On construction sites store piping in a designated location.
Page 128
AMAZON UNITARIO FD 5.3.3 Expanding copper piping ends Notes for installers ■ Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed. ■ Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head.
Page 129
AMAZON UNITARIO FD 5.3.5 Bending piping Bending copper piping reduces the number of brazed joints required and can improve quality and save material. Notes for installers Piping bending methods ■ Hand bending is suitable for thin copper piping (Ф6. 35mm - Ф12. 7mm).
Page 130
AMAZON UNITARIO FD 5.5 Brazing Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even compressor failure.
Page 131
AMAZON UNITARIO FD ... box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. Figure 3-5.6: Piping orientation during brazing Brazing Brazing Brazing Piping overlap during brazing Table 3-5.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints on piping of different diameters.
Page 132
AMAZON UNITARIO FD 5.6 Branch Joints 5.6.1 U-type branch joint Notes for installers ■ Use U-shaped branch joints as specified on the Figure 3-5.8: Branch joint orientation construction drawings – do not replace U-shaped branch U-shaped branching pipe joints with tee joints.
Page 133
AMAZON UNITARIO FD 5.6.2 Branch header Notes for installers ■ The content in this section is only for attention during the installation of branch header. ■ Please refer to the installation manual of branch header for detailed selection and installation requirements.
Page 134
AMAZON UNITARIO FD 5.7 Direction of refrigerant pipe connection Field piping can be connected in 4 directions. Before connecting, knock off the plate in the corresponding direction. Figure 3-5.13: Direction of refrigerant pipe connection right-front panel right-rear panel right-front panel...
Page 135
AMAZON UNITARIO FD 5.8.2 Procedure Notes for installers Warning Only use nitrogen for flushing. Using carbon dioxide risks leaving condensation in the piping. Oxygen, air, refrigerant, flammable gases and toxic gases must not be used for flushing. Use of such gases may result in fire or explosion.
AMAZON UNITARIO FD 5.9 Gastightness Test 5.9.1 Purpose To prevent faults caused by refrigerant leakage, a gastightness test should be performed before system commissioning. 5.9.2 Procedure Notes for installers Warning Only dry nitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be used for gastightness testing.
AMAZON UNITARIO FD 5.9.3 Leak detection Notes for installers To check for leaks: Vacuum leak test 1. Evacuate the system from the liquid and gas piping to –100.7 kPa (–1.007 bar)(5 Torr absolute) for more than 2 hours. 2. Once reached, turn off the vacuum pump and check that the pressure does not rise for at least 1 minute.
Page 138
AMAZON UNITARIO FD 5.10.2 Procedure Notes for installers During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C.
AMAZON UNITARIO FD 6 Drain Piping 6.1 Design Considerations Drain piping design should take account of the following considerations: ■ Indoor unit condensate drain piping needs to be of sufficient diameter to carry the volume of condensate produced at the indoor units and installed at a slope sufficient to allow drainage. Discharge as close as possible to the indoor units is usually preferable.
Page 140
AMAZON UNITARIO FD Figure 3-6.5: Drain piping air vents ■ Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should not come into direct contact with the ground. ■ Drain piping diameter should be not less than the indoor units’ drain piping connection.
Page 141
AMAZON UNITARIO FD Table 3-6.2: Vertical drain piping diameterst Nominal diameter PVC piping Capacity (L/h) Remarks (mm) PVC25 Branch piping only PVC32 PVC40 PVC50 1440 PVC63 2760 Branch or main piping PVC75 5710 PVC90 8280 6.4 Drain Piping for Units with Lift Pumps Drain piping for units with lift pumps should take account of the following additional considerations: ■...
AMAZON UNITARIO FD 6.6 Watertightness Test and Water Flow Test Once installation of a drainage piping system is complete, watertightness and water flow tests should be performed. Notes for installers Watertightness test ■ Fill the piping with water and test for leakages over a 24-hour period.
Page 143
AMAZON UNITARIO FD 7.1.4 Installation of piping insulation With the exception of joint insulation, insulation should be applied to piping before fixing the piping in place. Insulation at joints in refrigerant piping should be applied after the gastightness test has been completed.
AMAZON UNITARIO FD 8 Charging Refrigerant 8.1 Calculating Additional Refrigerant Charge The additional refrigerant charge required depends on the lengths and diameters of the outdoor and indoor liquid pipes. Table 3-8.1 shows the additional refrigerant charge required per meter of equivalent pipe length for different diameters of pipe.
AMAZON UNITARIO FD 8.2 Adding Refrigerant Notes for installers Caution ■ Only charge refrigerant after performing a gastightness test and vacuum drying. ■ Never charge more refrigerant than required as doing so can lead to liquid hammering. ■ Only use refrigerant R410A - charging with an unsuitable substance may cause explosions or accidents.
AMAZON UNITARIO FD 9 Electrical Wiring 9.1 General Notes for installers Caution ■ All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation. ■ Electrical systems should be grounded in accordance with all applicable legislation.
AMAZON UNITARIO FD 9.2 Power Supply Wiring Power supply wiring design and installation should adhere to the following requirements: ■ Separate power supplies should be provided for the indoor units and outdoor units. ■ Where five or more outdoor units are installed, additional residual current protection (leakage protection) should be installed.
■ When a single communication line is not long enough, the joint must be crimped or soldered, and the copper wire at the joint shall not be exposed. ■ Amazon unitario FD outdoor unit compatible with different generation indoor units, the communication connection type should follow table 3-9.1.
Page 149
AMAZON UNITARIO FD Figure 3-9.5: Communication wiring 9.3.1 Outdoor unit and indoor units’ P Q E communication Communication wiring design and installation should adhere to the following requirements: ■ 0.75mm three-core shielded cable should be used for communication wiring. Using other types of cable can lead to interference and malfunction.
Page 150
AMAZON UNITARIO FD 9.3.2 Outdoor unit and indoor units’ P Q communication Communication wiring design and installation should adhere to the following requirements: ■ 0.75mm two-core shielded cable should be used for communication wiring. Using other types of cable can lead to interference and malfunction.
Page 151
AMAZON UNITARIO FD 9.3.3 Outdoor unit and indoor units’ M1, M2 communication-IDUs unified power supplied Communication wiring design and installation should adhere to the following requirements when all IDUs unified power supplied: ■ 0.75mm two-core cable should be used for communication wiring when all the indoor units are unified power supplied.
Page 152
AMAZON UNITARIO FD Figure 3-9.10: M1 M2 communication wiring configuration – IDUs separate power supplied L1+La+Lx≤200m, L11+Lb+Ly≤200m, L21+Lc+L30≤200mm.Communication wiring 2*1.5mm Communication wire Master ODU Power wire Repeater 1 breaker Breaker T O D O W N ID U ··· (2-9)# IDU...
Page 153
AMAZON UNITARIO FD 9.3.5 Outdoor units’ XYE communication The outdoor unit’s combined system, and the communication lines between the ODUs must be connected in series. ■ 0.75mm two-core shielded cable should be used for communication wiring, and the length must not exceed 1200m.
AMAZON UNITARIO FD 10 Installation in Areas of High Salinity 10.1 Caution Do not install outdoor units where they could be directly exposed to sea air. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
AMAZON UNITARIO FD 11 Commissioning 11.1 Pre-commissioning Checks Before turning on the power to the indoor and outdoor units, ensure the following: ■ Installation Check if the unit is installed correctly to prevent strange noises and vibrations when the unit starts.
Page 156
AMAZON UNITARIO FD 11.2 Outdoor Unit Address and Communication Type Setting, Test Run Step 1: Power on Cover the lower panel of the ODU, and power on all IDUs and ODUs. Step 2: Enter commissioning mode When the ODU is first powered on, it displays "-. -. -. -.", which means the unit is not commissioned. Long press the “DOWN”...
Page 157
AMAZON UNITARIO FD Step 9: Other settings After completing the test run, you can set the relevant functions of the unit according to the actual functional requirements. For specific operations, please refer to related technical documents. If there is no special requirement, you can skip this step.
AMAZON UNITARIO FD 11.3 Troubleshooting during the Test Run. The test run is considered complete when there is no error code on the user interface or the outdoor unit display. When an error code is displayed, correct the operation based on the description in the error code table. Try to conduct the test run again to check that the exception has been corrected.
AMAZON UNITARIO FD 12 Appendix to Part 3 – System Operating Report A total of up to 11 report sheets should be completed for each system: ■ One Sheet A, one Sheet B and one Sheet C per system. ■ One Sheet D and one Sheet E per outdoor unit.
Page 160
AMAZON UNITARIO FD System Operating Report – Sheet A SYSTEM INFORMATION Project name and location Customer company System name Installation company Operating date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information OUTDOOR UNITS...
Page 161
AMAZON UNITARIO FD System Operating Report – Sheet B SYSTEM INFORMATION Project name and location Customer company System name Installation company Operating date Agent company Outdoor ambient temp. Commissioning engineer Model Serial no. Power supply (V) Outdoor unit information OUTDOOR UNITS...
Page 162
AMAZON UNITARIO FD System Operating Report – Sheet C Project name and location System name RECORD OF ISSUES SEEN DURING OPERATING Serial no. of Description of observed issue Suspected cause Troubleshooting undertaken relevant unit OUTDOOR UNIT FINAL CHECKLIST System check performed?
Page 163
AMAZON UNITARIO FD System Operating Report – Sheet D Project name and location System name Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode --.-- "Standby (ODU address+ IDU number)/frequency/special status" 0 (The default) 255 represents invalid 0.--...
Page 164
AMAZON UNITARIO FD System Operating Report – Sheet E Project name and location System name … table continued from previous page Observed values DSP1 Cooling Heating Parameters displayed on DSP2 Remarks content mode mode 34.-- EEVE position Actual value = value displayed × 4 35.--...