XRGI® 9 COMMISSIONING INSTRUCTION
S Y S T E M PA R A M E T E R S
Move the cursor to the desired field by using the ▲▼buttons and press
■
the user interface to activate the field.
■
Enter the value by using the
System
modus: Select the desired operating mode.
Meter source
When installing a Load Sharer S, Modbus Gateway or VPP Gateway
please follow the installation instructions of the respective component.
Trafo type
(only possible with meter source Trafo): Select the applied trafo type.
Land: Select ENGLAND.
Go to the next page by using the ▲▼buttons.
■
Power Unit
no.: Enter the Power Unit no. of the XRGI® system.
Gas
type: Enter the type of gas used.
Go to the next page by using the ▲▼buttons.
■
The XRGI® 9 system is designed for H-/L-gas. If LPG gas is used, turn the
throttle control lever on the power valve clockwise forward (away from
the engine).
H E AT P U M P S
If heat pumps are connected to the system, enter the effect of the heat pumps.
■
Move the cursor to
user interface to activate the field.
Enter the effect of the heat pump by using the ▲▼buttons and press
■
save the entry..
F R E Q U E N C Y R E S P O N S E
For the correct frequency response, set the standard of the country where the XRGI®
system is installed.
■
Move the cursor to
interface to activate the field.
Select the correct frequency by using the ▲▼buttons and press
■
entry.
COUNTRY
GERMANY
DENMARK
ENGLAND
ALL OTHER COUNTRIES
When selecting a standard, all values are automatically set for the applicable law. The
specified default values can be adjusted as required.
▲▼
buttons and press
(only possible with powerled): Select the applied meter.
Heat pumps
by using the
▲▼
Type
by using the
OK
ESC
to save the entry.
▲▼
OK
buttons and press
on the
ESC
OK
buttons and press
on the user
ESC
to save the
STANDARD
VDE 4105:2018
TB 27 04 2019
TF 3.2.1
TF 3.2.3
G98:2018
G99:2018
None
SYSTEM PARAMETERS
on
XRGI-ID:
XRGI type:
Max power:
System modus:
Meter source:
Trafo type:
Country:
Send
SYSTEM PARAMETERS
Power Unit no.:
Gas type:
Catalyst type:
HEAT PUMPS
Heat pump 1:
to
FREQUENCY RESPONSE
Type:
FREQUENCY RESPONSE
Type:
Frequency treshold:
Droop setting:
Reference power:
Activation delay:
Reg. belov min load:
Return gradient:
VERSION 1.0 2019
1/6
1234567890
XRGI 9
9.1 kW
Powerled
Trafo
50/5
ENGLAND
2/6
1234567890
H
No stud
5/6
0.5 kW
6/6
G98:2018
6/6
G98:2018
50.40 Hz
10.0 %
Rated power
0.0 Sek
Continue
10 %
25