Bleeding - EC POWER XRGI 6 Commissioning Instruction

Hide thumbs Also See for XRGI 6:
Table of Contents

Advertisement

VERSION 1.0 2019
3.2.1
B L E E D I N G
Open the Power Unit and remove the Q-Heat Distributor cover.
Check whether all four valves on the manifold are open on the Q-Heat Distributor.
Open any closed valves.
Q - H E AT D I S T R I B U T O R
Use a bleed key to bleed the storage circuit on the Q-Heat Distributor. Attach a
hose to the bleed screw to divert any leaking heating water and then use an
mm
wrench to loosen the bleed screw.
When only heating water escapes from the bleed screw, tighten the screw.
Add XRGI® Engine Coolant to the expansion vessel on the Q-Heat Distributor. Add
up to the maximum mark.
P O W E R U N I T
Bleed the engine circuit at the air pot on the Power Unit. Attach a hose to the
bleed screw to divert any leaking XRGI® Engine Coolant and then use an
wrench to loosen the bleed screw.
Bleed until only XRGI® Engine Coolant and no air escapes.
When only XRGI® Engine Coolant escapes from the bleed screw, tighten the screw
and check if there is still sufficient XRGI® Engine Coolant in the expansion vessel. If
necessary, refill XRGI® Engine Coolant to the maximum mark.
i Q - C O N T R O L PA N E L
Press any key on the user interface to activate the display and enter the menu.
Press any button on the user interface again to enter the main menu.
Move the cursor to
user interface.
14
by using the ▲▼buttons and press
Technician
XRGI® 6 COMMISSIONING INSTRUCTION
11
11 mm
1234567890
Consumption
98 %
13:10:16
22.05.2019
OK
on the
Heat pumps
Start/Stop
Statistics
1/1
10.1 kW
Production:
9.9 kW
MAIN MENU
1/1
Operating info
Settings
Modem call
Technician

Advertisement

Table of Contents
loading

Related Products for EC POWER XRGI 6

This manual is also suitable for:

Xrgi 9Xrgi 15Xrgi 20X060001X090001X150001 ... Show all