XRGI® 6 COMMISSIONING INSTRUCTION
S Y S T E M PA R A M E T E R S
Move the cursor to the desired field by using the ▲▼buttons and press
the user interface to activate the field.
Enter the value by using the
System
modus: Select the desired operating mode.
Meter source
When installing a Load Sharer S, Modbus Gateway or VPP Gateway
please follow the installation instructions of the respective component.
Trafo type
(only possible with meter source Trafo): Select the applied trafo type.
Land: Select ENGLAND.
Go to the next page by using the ▲▼buttons.
Power Unit
no.: Enter the Power Unit no. of the XRGI® system.
Gas
type: Enter the type of gas used.
Go to the next page by using the ▲▼buttons.
The XRGI® 6 system is designed for L-gas. If H or LPG gas is used, turn the
throttle control lever on the power valve clockwise forward (away from
the engine).
H E AT P U M P S
If heat pumps are connected to the system, enter the effect of the heat pumps.
Move the cursor to
user interface to activate the field.
Enter the effect of the heat pump by using the ▲▼buttons and press
save the entry..
F R E Q U E N C Y R E S P O N S E
For the correct frequency response, set the standard of the country where the XRGI®
system is installed.
Move the cursor to
interface to activate the field.
Select the correct frequency by using the ▲▼buttons and press
entry.
COUNTRY
GERMANY
DENMARK
ENGLAND
ALL OTHER COUNTRIES
When selecting a standard, all values are automatically set for the applicable law. The
specified default values can be adjusted as required.
▲▼
buttons and press
(only possible with powerled): Select the applied meter.
Heat pumps
by using the
▲▼
Type
by using the
OK
ESC
to save the entry.
▲▼
OK
buttons and press
on the
ESC
OK
buttons and press
on the user
ESC
to save the
STANDARD
VDE 4105:2018
TB 27 04 2019
TF 3.2.1
TF 3.2.3
G98:2018
G99:2018
None
SYSTEM PARAMETERS
on
XRGI-ID:
XRGI type:
Max power:
System modus:
Meter source:
Trafo type:
Country:
Send
SYSTEM PARAMETERS
Power Unit no.:
Gas type:
HEAT PUMPS
Heat pump 1:
to
FREQUENCY RESPONSE
Type:
FREQUENCY RESPONSE
Type:
Frequency treshold:
Droop setting:
Reference power:
Activation delay:
Reg. belov min load:
Return gradient:
VERSION 1.0 2019
1/6
1234567890
XRGI 6
6.1 kW
Powerled
Trafo
50/5
ENGLAND
2/6
1234567890
H
5/6
0.5 kW
6/6
G98:2018
6/6
G98:2018
50.40 Hz
10.0 %
Rated power
0.0 Sek
Continue
10 %
17