Pressure and flow control system SYDFE1 series 2X, 3X | Mounting
VT5041-3X...
Bosch Rexroth AG, Edition 10.2021, RE 30011-B
VT5041-3X...
Jumper
J8 ON
Shield
Cable type:
e.g. LiYCY 5 x 0.25
Attention: The order of wire
assignment is essential!
Fig. 26: Cabling for cable lengths up to 50 m
If distances of 50 m or greater must be covered, we recommend that twisted
pair cables be installed. In this case, jumper J8 must not be set on control
electronics VT 5041-3X.
Recommended cable type: LiYCY(TP) 2 x 2 x 0.25 mm²
Shield
Fig. 27: Cabling in case of cable lengths of more than 50 m or twisted-pair cable
Valve position
transducer
Shielding effect
gr = gray
ws = white
bn = brown
gb = yellow
gn = green
Valve position
transducer