respond to one alarm first and then respond to the next one after the user-defined interval. You
can set the on SEQUENCE submenu from 1 to 200 seconds.
3. Configure the alarm rest delay.
If there's a linkage action has already been triggered by an alarm input, the speed dome will
only respond to the input from the same channel again after the user-defined reset delay time.
This is the rest time that the speed dome considers an alarm to be active when it's physically
cleared. You can set the DELAY TIME from 0 to 300 seconds.
4. Resume the dome activity.
You can set ALARM RESUME to ON to enable the speed dome to resume its previous activity
after the triggered actions finished.
 If the speed dome is moving when a linkage action is triggered, it will stop at the current
position and resume from this position after the linkage action finishes.
 The speed dome can be configured to resume the PTZ positions, focus and iris value.

3.5.3 Configuring Alarm Output

Purpose:
An alarm output is a configurable alarm output interface on the speed dome back box which can
connect and trigger another alarm device to operate.
Steps:
1. Enter the alarm output configuration submenu:
MAIN MENUS > DOME SETTINGS > ALARM OUTPUT
2. Click IRIS+ to edit the status of the alarm outputs. You can set the alarm output type as OPEN
(normally open) and CLOSE (normally closed).
There is 1 alarm output configurable; configuring the alarm output 2 will be invalid.
3. Move the cursor to DWELL TIME to set the duration of the alarm output signal. The configurable
rage is 0~60 seconds.
4. Link the alarm output to the configured alarm.
© Hikvision
ALARM OUTPUT
ALARM OUTPUT 1
DWELL TIME
ALARM OUTPUT 2
DWELL TIME
BACK
Figure 3-21 Configure the Alarm Output
CLOSE
2
OPEN
0
EXIT
32