10-channel universal voltage input & current input, thermocouple input module (8 pages)
Summary of Contents for ICP DAS USA M-7064
Page 1
Congratulations on purchasing the M-7064(D) the most popular automation solution for remote monitoring and control applications. This Quick Start Guide will provide information needed to get started with the M-7064(D). Please also consult the User Manual for detailed information on the setup and use of the M-7064(D).
Page 3
Make sure the INIT* wire to (B)GND. ---------------------------------------------------------------------------------- Connecting to the PC and the Power Supply M-7064(D) series modules are equipped with an RS-485 port that can be used to connect to an RS-232/USB converter to connect the module to a host...
Page 4
Using the DCON Utility Pro to Initialize the M-7064(D) Module The M-7064(D) is an I/O module based on the DCON protocol, meaning that you can use the DCON Utility Pro to easily initialize it. Step 1: Run the DCON Utility Pro Double-click the DCON Utility shortcut on your desktop.
Page 6
ICP DAS CO., LTD. Step 4: Connect to the M-7064(D) After clicking on the name of the module in the list, a dialog box would be display. Step 5: Initialize the M-7064(D) module Set the “Address” field in the dialog box to 1 and then click “Setting” button to save the settings.
Page 7
---------------------------------------------------------------------------------- Starting the Module Operation After rebooting the M-7064(D) module, search for the module to make sure the settings have been changed. You can double click on the name of the module in the list to open the configuration dialog box.