Rated Capacity Test (Cooling mode)
Under Cooling Mode, set the air conditioner at High Fan Speed and set the
temperature to 17 C, then press the TURBO button 6 times within 10
seconds (be sure the indoor unit buzzes 6 times). The system will enter
Rated Capacity Test mode. The buzzer will keep on sounding for 2 seconds
when the fan speed reaches rating speed and the compressor rotates at
rating speed.
The air conditioner can enter the Rated Capacity Test mode only when all
the above conditions are met.
This mode will automatically de-activate after 5 hours.
During the Rated Capacity Test mode, if common protection, ambient
temperature limitation for start-up and rotation frequency or de-frost
protection occurs, the test must be stopped.
Rated Capacity Test (Heating mode)
Under Heating Mode, set the air conditioner at High Fan Speed and set the
temperature to 30 C, then press the TURBO button 6 times within 10
seconds (be sure the indoor unit buzzes 6 times). The system will enter
Rated Capacity Test mode. The buzzer will keep on sounding for 2 seconds
when the fan speed reaches rating speed and the compressor rotates at
rating speed.
The air conditioner can enter the Rated Capacity Test mode only when all
the above conditions are met.
This mode will automatically de-activate after 5 hours.
During the Rated Capacity Test mode, if common protection, ambient
temperature limitation for start-up and rotation frequency or de-frost
protection occurs, the test must be stopped.
23