Mitsubishi Electric PAR-W21MAA Installation Manual

Mitsubishi Electric PAR-W21MAA Installation Manual

Hide thumbs Also See for PAR-W21MAA:

Advertisement

GB
WT05312X01
CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO
WATER, and FLOW TEMP. CONTROLLER Remote Controller
Installation Manual
This instruction manual describes how to install the Remote Controller for CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO WATER, and
FLOW TEMP. CONTROLLER. Please read this manual thoroughly and install the remote controller accordingly. For information on how to wire and
install CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO WATER, and FLOW TEMP. CONTROLLER Remote Controller, refer to the
installation manual. After the installation, hand over this manual to users.
1 Safety Precautions
● Read these Safety Precautions and perform installation work accordingly.
● The following two symbols are used to dangers that may be caused by incorrect use and their degree:
WARNING
This symbol denotes what could lead to serious injury or death if you misuse the PAR-W21MAA.
CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAR-W21MAA.
● After reading this installation manual, give it and units installation manual to the end user.
● The end user should keep this manual and units installation manual in a place where he or she can see it at anytime. When someone moves or
repairs the PAR-W21MAA, make sure that this manual is forwarded to the end user.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric
shock or fire.
Install in a place which is strong enough to withstand the weight of the
PAR-W21MAA.
Any lack of strength may cause the PAR-W21MAA to fall down, resulting in
personal injury.
Firmly connect the wiring using the specified cables. Carefully check
that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PAR-W21MAA by yourself.
Any deficiency caused by your modification or repair may result in an
electric shock or fire.
Consult with your dealer about repairs.
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAR-W21MAA may
cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and sulfuric
gas may deteriorate the performance significantly or give damage to the
component parts.
When installing the remote controller in a hospital or communication
facility, take ample countermeasures against noise.
Inverters, emergency power supply generators, high-frequency medical
equipment, and wireless communication equipment can cause the remote
controller to malfunction or to fail. Radiation from the remote controller may
effect communication equipment and prevent medial operations on the
human body or interfere with image transmission and cause noise.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty etc.
Any dew, moisture, insects entering the unit may cause an electric shock or
a malfunction.
Do not install in any place at a temperature of more than 40°C [104°F]
or less than 0°C [32°F] or exposed to direct sunlight.
Doing so may cause deformation or malfunction.
2 Confirming the Supplied Parts
Confirm that the box includes the following parts, in addition to this installation manual:
1. Remote controller (cover, body) ................................................................................ 1
2. Cross recessed pan head screw (M4 u 30) ............................................................... 2
3. Wood screw (4.1 u 16, used for directly hooking to the wall) .................................... 2
4. Caution label (in 16 languages)................................................................................. 1
Use the cable specified in the Installation Manual that comes with the units for remote controllers.
WARNING
Ensure that installation work is done correctly following this
installation manual.
Any deficiency caused by installation may result in an electric shock or fire.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation may
result in an electric shock or fire.
Do not move and re-install the PAR-W21MAA yourself.
Any deficiency caused by installation may result in an electric shock or fire.
Ask your distributor or special vendor for moving and installation.
To dispose of this product, consult your dealer.
CAUTION
Do not apply AC100V or AC200V to the remote controller. The
maximum voltage that can be applied to the remote controller is 12V.
The remote controller may be damaged or may generate heat and cause a
fire.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may
cause an electric shock or a malfunction.
Do not install in any place where acidic or alkaline solution or special
spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
PAR-W21MAA
Remote controller cover
Remote controller body
1

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PAR-W21MAA

  • Page 1 This symbol denotes what could lead to serious injury or death if you misuse the PAR-W21MAA. CAUTION This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAR-W21MAA. ● After reading this installation manual, give it and units installation manual to the end user.
  • Page 2: How To Install

    3 How To Install 1. Choose a place in which to install the remote controller (switch box). Be sure to observe the following steps: Extra space (1) When installing on either the switch box or the wall, allow extra space around the remote controller as External size around remote of remote...
  • Page 3: Function Selection

    During test run, the RUN lamp remains on. BACK MONITOR/SET CHECK TEST 4. If trouble occurred during the test run, refer to the “Test Run” section PAR-W21MAA CLOCK CLEAR [TEST] button of the unit installation manual. 5 Function Selection (1) Function selection of remote controller The setting of the following remote controller functions can be changed using the remote controller function selection mode.
  • Page 4 G button. Mode selection BACK MONITOR/SET CHECK TEST See [4]-3. (3) Timer function setting (“WEEKLY TIMER”) (“MODE PAR-W21MAA CLOCK CLEAR SELECTION”) See [4]-3. (4) Contact number setting for error situation (“CALL.”) Press the E button. See [4]-3. (5) Temp off set setting (“TEMP OFF SET FUNCTION”) Press the D button.
  • Page 5: Initial Setting

    (3) Timer function setting (5) Temp off set setting • To switch the setting, press the [ ON/OFF] button (Choose one of • To switch the following settings, press the [ ON/OFF] button. 1 ON : The setback amount setting is displayed under the water the followings.).
  • Page 6 : Sets the water temperature to 1°C when starting operation in Heating mode. 1. Water Temp Heating 2. Water Temp Heating ECO No.1 : Sets the water temperature to 2°C for an outside air temperature of 3°C when operating in Heating ECO mode. 3.
  • Page 7: Self Check

    INITIAL SETTING CIR.WATER BACK MONITOR/SET CHECK TEST PAR-W21MAA CLOCK CLEAR 1 Switch to the self check mode. 2 Set the address or refrigerant address No. you want to self check. When the [CHECK] H button is pressed twice successively within...
  • Page 8: Remote Controller Check

    Approximately 30 seconds later, the remote controller returns to the state before remote controller check. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Authorized representative in EU: MITSUBISHI ELECTRIC EUROPE B.V. HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.

Table of Contents