TTR31, TTR35
Function
group
Analog
output
Min. distance between SETL and SETU: 20 °C/K (36 °F)
!
Note!
The function group 4-20 is only available if the 4 to 20 mA analog output (
the function group
5.1.7 Settings for service functions
Function
group
Service
functions
Endress+Hauser
Function
Error current
or
under
Function
Locking code
Change locking
code
Reset
Revision counter
Last device status
Settings
or
.
Settings
Operation
Description
Current value in event
of error:
MIN = ≤ 3.6 mA
MAX = ≥ 21.0 mA
HOLD = last value
Factory setting:
MAX
) is selected in
Description
Enter the locking code
for enabling the device.
Freely selectable code
1...9999.
0 = no locking;
A locking code already
assigned can only be
changed by first entering
the old code for enabling
the device.
Reset all entries to the
factory setting
Increases by 1 with each
configuration
Displays the last device
status to occur ≠ 0