Endress+Hauser Thermophant T TTR31 Operating Manual page 19

Temperature switch
Hide thumbs Also See for Thermophant T TTR31:
Table of Contents

Advertisement

TTR31, TTR35
Function
group
Output 1
Output 2,
as option
Min. distance between SP and RSP: 0.5 °C/K (0.9 °F)
5.1.6 Settings for output - 1x switch output and 1x analog output (4 to 20 mA)
Function
group
Output 1
Output 2,
as option
Endress+Hauser
Function
Switch-back point
value
Switch point delay
Switch-back point
delay
Function
Switching
characteristic
Switch point value
Settings
Description
Switch-back point
-50 to 149 °C
(-58 to 300 °F)
in increments of 0.1 °C
(0.18 °F)
Delay time
0...99 s
in increments of 0.1 s
Factory setting: 0 s
Delay time 0...99 s
in increments of 0.1 s
Factory setting: 0 s
Settings
Description
WINC:
window/NC contact
HYNC:
hysteresis/NC contact
WINO:
window/NO contact
HYNO:
hysteresis/NO contact
4 - 20: analog output
Factory setting: HYNO
Switch point
-49.5 to 150 °C
(-57.1 to 302 °F)
in increments of 0.1 °C
(0.18 °F)
Operation
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thermophant ttr35Thermophant t ttr35

Table of Contents