INFOSEC C3 MPPT User Manual page 21

Table of Contents

Advertisement

Available languages

Available languages

20
Backlight control
Beeps while the primary
22
source is interrupted
Overload bypass:
When enabled, the unit will
23
transfer to line mode if an
overload occurs in battery
mode.
25
Record Fault code
Bulk charging voltage
26
(C.V voltage)
27
Floating charging voltage
29
Low DC cut-off voltage
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 06 15 AA 59 203 33
Stay at latest screen
Backlight on
(default)
Alarm on (default)
Bypass disable
(default)
Record enable
24V models default setting: 28.2V
48V models default setting: 56.4V
If self-defined is selected in program 5, this program can be
set. The setting range is from 24.0V to 29.2V for 24V models
and 48.0V to 58.4V for 48V models.
24V models default to 27.0V
48V models default setting: 54.0V
If self-defined is selected in program 5, this program can be
set. The setting range is from 24.0V to 29.2V for 24V models,
48.0V to 58.4V for 48V models.
24V models default setting: 21.0V
48V models default setting: 42.0V
If self-defined is selected in program 5, this program can be
set. The setting range is from 20.0V to 24.0V for 24V model,
40.0V to 48.0V for 48V model. Low DC cut-off voltage will be
fixed to the setting value no matter what percentage of load
is connected.
If selected, the display screen will stay
at the latest screen the user checked.
Backlight off
Alarm off
Bypass enable
Record disable (default)
21